| 2006-03-18 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | DENIED 2ND TIME |
| | 1) |
| | 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED |
| | BY THE BUILDING OFFICAL. CONSTRUCTION |
| | DOUCMENTS SHALL BE OF SUFFICENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT ITWILL CONFORM TOTHE |
| | PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS |
| | AS DETERMINED BY THE BUILDING OFFICAL ( |
| | SEE ALSO SECTION 106.3.5) |
| | |
| | 2)TAB 403 MINIMUM FACILITIES. |
| | ONE AUTOMATIC CLOTHES WASHER CONNECTION |
| | PER DWELING UNIT. |
| | 3) SHOW THE FIXTURE CLEARANCE |
| | 405.3.1 WATER CLOSETS, URINALS, |
| | LAVATORIES AND BIDETS. |
| | A WATER CLOSET, URINAL, LAVATORY OR |
| | BIDET SHALL NOT BE SET CLOSER THAN 15 |
| | INCHES (381 MM) FROM ITS CENTER TO ANY |
| | SIDE WALL, PARTITION, VANITY OR OTHER |
| | OBSTRUCTION, OR CLOSER THAN 30 INCHES |
| | (762 MM) CENTER-TO-CENTER BETWEEN WATER |
| | CLOSETS, URINALS OR ADJACENT FIXTURES. |
| | THERE SHALL BE AT LEAST A 21-INCH (533 |
| | MM) CLEARANCE IN FRONT OF THE WATER |
| | CLOSET, URINAL OR BIDET TO ANY WALL, |
| | FIXTURE OR DOOR. WATER CLOSET |
| | COMPARTMENTS SHALL NOT BE LESS THAN 30 |
| | INCHES (762 MM) WIDE OR 60 INCHES (1524 |
| | MM) DEEP. THERE SHALL BE AT LEAST A |
| | 21-INCH (533 MM) CLEARANCE IN FRONT OF A |
| | LAVATORY TO ANY WALL, FIXTURE OR DOOR |
| | (SEE FIGURE 405.3.1). |
| | 4)BACK FLOW PREVENTER REQUIRED ON WATER |
| | SERVICE, LOCAL ORDINANCE #2853-95 |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |
| | |
| | |