| Plan Review Notes For Permit 05111101 |
| Permit Number |
05111101 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-09 00:00:00 | **** UNSAT 2ND REVIEW ** | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | 1) NOTE: PLEASE SEE VALUE SHALL BE BASED | | | ON ALL LABOUR AND MATERIALS. | | | INCLUSIVE OF ANY OWNER SUPLLIED | | | EQUIPMENT. | | | 108.3 | | | PLEASE SEE A VALUE OF $15,200 IS NOW | | | PLACED ON APPLICATION WHICH STILL SEEMS | | | LOW FOR GEN/ ATS ETC. | | | PLEASE KNOW, A VALUE WILL BE APPLIED BY | | | THIS OFFICE PER "MARSHALL'S SWIFT GUIDE" | | | IF NEEDED. | | | | | | 2) NOTE: PLEASE SUBMIT ALL SPECS FOR | | | GEN., ATS AND FUEL TANK. | | | PLEASE SEE ONLY THE SPECS FOR THE GEN | | | WHICH DOES NOT CORRELATE WITH THE KW | | | RATING OF THE GEN. SHOWN ON PLANS. | | | 50 OR 60? | | | PLEASE ALSO SEE SPECS FOR WHETHER PROOF | | | ENCLOSURE WAS SUBMITTED WHICH IS OK. | | | 215.5 | | | | | | 3) NOTE: PLEASE KNOW, THIS PERMIT IS FOR | | | THE INSTALLATION OF THE GEN ONLY/SLAB, | | | AND A "GEN-ELEC" PERMIT WILL BE | | | REQUIRED. THIS PERMIT APPLICATION WILL | | | REFERENCE THESE PLANS ONCE ISSUED, AND | | | THE PERMIT WILL BE A "TURN AROUND | | | PERMIT" ISSUED THE SAME DAY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|