| Plan Review Notes For Permit 05111101 |
| Permit Number |
05111101 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-25 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE MANUFACTURERS | | | SUBMTITTAL DATA FOR THE GENERATOR. | | | | | | 2.PER NFPA 37 SECTION 4.1.4, ENGINES | | | LOCATED OUTDOORS SHALL BE LOCATED AT | | | LEAST 5 FT FROM OPENINGS IN WALLS AND 5 | | | FT FROM STRUCTURES HAVEING COMBUSTIBLE | | | WALLS.AS MINIMUM SEPARATION IS NOT | | | REQUIRED IF THE FOLLOWING CONDITIONS ARE | | | MET: 1) THE ADJACENT WALL OF THE | | | STRUCTURE HAS A FIRE RESISTANCE RATING | | | OF AT LEAST 1 HOUR.2)THE WEATHERPROOF | | | ENCLOSURE WILL NOT IIGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | | | | 3.PLEASE INDICATE DISTANCE OF THE | | | GENERATOR EXHAUST TO ANY OPENINGS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|