| 2005-12-24 00:00:00 | ********** UNSAT *********** |
| | |
| | |
| | 1)NOTE: PLEASE SEE VALUATION FOR |
| | PERMITTING AND COMPLETE SCOPE OF WORK |
| | SHALL INCLUDE ALL LABOR AND MATERIALS. |
| | PLEASE SEE THE VALUE APPLIED FOR ($5200) |
| | IS WAY TOO LOW. |
| | FBC ADMIMISTRATIVE SEC 108.3 AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | CUT/SPEC SHEETS FOR SAID GENERATOR, ATS, |
| | AND SUB-BASE FUEL TANK. |
| | PLEASE BE SURE ALL LISTINGS ARE SHOWN |
| | AND ALL ARE LISTED BY A NRTL. |
| | |
| | 3)NOTE: PLEASE PROVIDE A MEANS OF |
| | DISCONNECT FOR FEEDERS FROM GEN INT |
| | EXISTING SERVICE., |
| | THIS DISCONNECTING MEANS MUST BE RATED |
| | FOR LOAD SERVED, SERVICE RATED, GROUPED |
| | WITH EXISTING MAINS ETC. |
| | PLEASE SEE 225.31- 225.39. |
| | |
| | 4)NOTE: PLEASE INCLUDE OCP AT GENERATOR |
| | IN ORDER TO VERIFY CONDUCTORS, LOADS, |
| | ETC. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE PROVIDE COMPLETE LOAD |
| | CALCUALTIONS FOR SAID LOADS TO BE |
| | IMPLIED ON GENERATOR. |
| | PLEASE SEE 702.5, WHICH PERMIT THE |
| | CUSTOMER TO SELECT LOADS, HOWEVER ON A |
| | ATS SYSTEM, GENERATOR MUST STILL BE |
| | RATED FOR ALL LOADS TO BE SERVED. |
| | PLEASE BE SURE ANY A/C/ HEAT, MOTOR |
| | LOADS ARE FIGURED AT 100%. |
| | ** LOAD SHEDDING IS PERMITTED, HOWEVER |
| | PLEASE SHOW DETAILS IF THIS IS DONE. |
| | |
| | 6)NOTE: PLEASE KNOW, THE CGC APPLIED TO |
| | PERMIT IS ONLY PERMITTED TO PLACE SLAB |
| | AND GEN AND IS NOT PERMITTED TO DO ANY |
| | OTHER ELECTRICAL WORK. |
| | PLEASE SEE THAT AN ELECTRICAL CONTRACTOR |
| | WAS NOT SIGNED ON PERMIT APPLICATION. |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |