Plan Review Notes
Plan Review Notes For Permit 05111074
Permit Number 05111074
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-20 00:00:00 
  
 DENIED
  
  
 1) RETAINING WALLS SHALL COMPLY WITH
 1806 OF THE 2004 FL BLDG CODE EFFECTIVE
 OCT.1, 2005
  
 2) STATE ALL PERTINENT INFORMATION ON
 DRAWINGS SUCH AS WALL HEIGHT, ELEVATION
 DIFFERENCE BETWEEN SIDEWALK AND EARTH TO
 BE RETAINED, ETC.
  
 3) MASONARY SHALL BE FULLY GROUTED WITH
 A MINIMUM OF 1500 PSI. SHOW ON DRAWINGS
  
 4) RETAINING WALLS SHALL BE DESIGNED TO
 RESIST THE SOIL LOADS IN SECTION 1610 OF
 THE 2004 FL BLDG CODE AND SHALL INCLUDE
 THE HYDROSTATIC PRESSURE UNLESS DRAINAGE
 IS PERMITTED AND PROVIDED
  
  
 BLDG PLAN REVIEW