| Plan Review Notes For Permit 05111074 |
| Permit Number |
05111074 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-20 00:00:00 | | | | | | | DENIED | | | | | | | | | 1) RETAINING WALLS SHALL COMPLY WITH | | | 1806 OF THE 2004 FL BLDG CODE EFFECTIVE | | | OCT.1, 2005 | | | | | | 2) STATE ALL PERTINENT INFORMATION ON | | | DRAWINGS SUCH AS WALL HEIGHT, ELEVATION | | | DIFFERENCE BETWEEN SIDEWALK AND EARTH TO | | | BE RETAINED, ETC. | | | | | | 3) MASONARY SHALL BE FULLY GROUTED WITH | | | A MINIMUM OF 1500 PSI. SHOW ON DRAWINGS | | | | | | 4) RETAINING WALLS SHALL BE DESIGNED TO | | | RESIST THE SOIL LOADS IN SECTION 1610 OF | | | THE 2004 FL BLDG CODE AND SHALL INCLUDE | | | THE HYDROSTATIC PRESSURE UNLESS DRAINAGE | | | IS PERMITTED AND PROVIDED | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|