| Plan Review Notes For Permit 05111071 |
| Permit Number |
05111071 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-03 10:48:56 | *****UNSAT***** | | | | | | | | | | | | 1.AREA 5, LEVEL 3 STACK, SHOWS A SAFETY MARGIN OF | | | ONLY 4.703 PSI.AS PER WPBFR, A SAFETY MARGIN OF AT | | | LEAST 5.0 PSI IS REQUIRED. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|