| 2006-07-23 00:00:00 | ***** UNSAT ***** |
| | |
| | ** PLEASE KNOW, IT IS UNCLEAR WHERE |
| | PLANS FROM THE PREVIOUS SUBMITTED SETS |
| | ARE AS THOSE WERE REVIEWED BY MR. BILL |
| | TROBAUGH. PLEASE KNOW, THIS REVIEW IS |
| | BASED ON PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE 2004 RESIDENTIAL |
| | CODE R313 AND PLEASE SHOW A LAYOUT FOR |
| | ALL EXISTING BEDRMS WHICH WILL REQUIER |
| | ALL SD'S TO BE BROUGHT UP TO THE CURRENT |
| | CODE PER NFPA-72 11.5.1.1,11.8.3 |
| | PLEASE INDICATE IF THESE ARE GOING TO BE |
| | NEW OR ARE EXISTING MEETING THE CURRENT |
| | CODE AND BEING TIED INTO NEW SD'S SHOWN |
| | ON THESE PLANS. |
| | |
| | 2) NOTE: PLEASE SEE 210.11C2, 220.16 AS |
| | THE MIN VA FOR WASHER/LAUNDRY IS NOT |
| | CORRECT. PLEASE ADJUST. |
| | |
| | 3) NOTE: PLEASE CORRELATE ALL ELECTRICAL |
| | HEAT FOR AHU'S WITH MECHANCIAL PLANS. |
| | PLEASE SEE KW RATINGS DO NOT MATCH. THIS |
| | WILL AFFECT ELECTRICAL CALCUALATIONS. |
| | PLEASE ALSO SEE 424.3B FOR MIN OCP |
| | REQUIRED @125% FOR HEAT STRIPS. |
| | PLEASE ADJUST CALCULATIONS PER 220.31B. |
| | |
| | 4) NOTE: PLEASE SEE MANY GEN LIGHTING |
| | CIRCUITS ARE BEING SHOWN WITH A LOAD OF |
| | 1500 VA ON 15A CIRCUITS, HOWEVER SHOWS |
| | #12?? PLEASE KNOW, A MAX OF 1440VA IS |
| | PERMITTED ON A 15A CIRCUIT, UNLESS THESE |
| | ARE INDEED 20A CIRCUITS AS #12 IS |
| | TYPICALLY FOR 20A CIRCUITS? PLEASE KNOW, |
| | IF CIRCUIT IS GOING TO BE 20A, THEN A |
| | PERMITTED LOAD OF 1920VA IS PERMITTED. |
| | PLEASE CLARIFY AND COORELATE WHICH ONES. |
| | 240.4,310.16, FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE CLARIFY THE AMOUNT OF |
| | SMALL APPLIANCE CIRCUITS BEING SHOWN?? |
| | PLEASE SEE PANEL SCHEDULE SHOWS ONE SM |
| | APPL AND ONE GFI APPL, ALTHOUGH THERE |
| | ARE WHAT SEEMS TO BE SMALL APPL CIRCUITS |
| | ON 3RD FLR ALONG WITH FRIG. PLEASE SEE |
| | PANEL SCHEDULE ONLY SHOWS ONE FRIG. |
| | PLEASE SEE 210.11C1,210.52B1,220.16 AS A |
| | MIN OF 1500VA IS REQUIRED FOR "EACH" OF |
| | SMALL APPPLIANCE CIRCUITS PROVIDE AND A |
| | MIN OF TWO ARE REQUIRED IN KITCHEN ON |
| | FIRST FLR. |
| | PLEASE ALSO SEE THAT THE DINING RM |
| | RECEPTS SHALL ALSO BE FIGURED PER ABOVE |
| | CODES NOTED. PLEASE ADJUST. |
| | |
| | 6) NOTE: PLEASE SEE THE FOLLOWING CODES |
| | SHALL BE SPECIFIED ON PLANS. |
| | NFPA-70 (NEC) 2002 NAD NFPA-72 2002. |
| | PLEASE KNOW, PLANS ONLY MENTIONS TO |
| | NEC. |
| | 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE REDLINED PLANS FOR |
| | MISSING RECEPT ALONG WALL IN MASTER |
| | BEDRM. |
| | 210.52 |
| | |
| | 8) NOTE: PLEASE SEE CIRCUITS ON PANEL |
| | SCHEDULE SHALL BE SPECIFIC TO RMS AND |
| | AREAS IN WHICH THEY FEED. |
| | IE: MASTER BEDRM LTS, LIVING RM RECEPTS |
| | ETC. IT IS KNOWN, THAT CIRCUITS WILL BE |
| | REVISED DURING THE CONSTRUCTION PROCESS, |
| | HOWEVER CIRCUITS SHALL BE SPECIFIC AT |
| | THIS TIME. 408.4. |
| | PLEASE ALSO BE SURE TO LIST ALL THE |
| | REQUIRED ARC FAULT PROTECTED CIRCUITS ON |
| | PANEL SCHEDULE. 210.12B, 408.4 |
| | |
| | 9) NOTE: PLEASEGO OVER CALCULATIONS, |
| | AS THE LOAD SHOWN AFTER TAKING THE |
| | DE-RATINGS SHOWS 190A'S. PLEASE KNOW, |
| | LOADS FOR A/ C ARE NOT SHOWN AS NEEDED |
| | AND SHOWN ON MECHANICAL PLANS, ALONG |
| | WITH MIN SM APPL/DINING LOADS ETC. |
| | PLEASE SEE 90.8 AS THE CODEREQUIRES |
| | SPACE FOR FUTURE LOADS ETC. |
| | ** PLEASE KNOW, IF LOAD EXCEEDS ANY |
| | FURTHER THAN SHOWN A LARGER SERVICE MAY |
| | BE REQUIRED. PLEASE CHECK CALCULATIONS |
| | AS SHOWN. |
| | |
| | 10) NOTE: PLEASE SHOW THE LOCATION OF |
| | THE 200A DISCONNECT AS SHOWN ON RISER. |
| | 110.26,240.24 |
| | |
| | 11) NOTE: PLEASE SEE MISSING LT REQUIRED |
| | FOR AHU(S) ON FIRST FLR PER 210.70. |
| | PLEASE SEE 3RD FLR AHU MISSING RECEPT IN |
| | ATTIC AS LT IS SHOWN. 210.63 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |