Plan Review Notes
Plan Review Notes For Permit 05111033
Permit Number 05111033
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-23 00:00:00***** UNSAT *****
  
 ** PLEASE KNOW, IT IS UNCLEAR WHERE
 PLANS FROM THE PREVIOUS SUBMITTED SETS
 ARE AS THOSE WERE REVIEWED BY MR. BILL
 TROBAUGH. PLEASE KNOW, THIS REVIEW IS
 BASED ON PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE 2004 RESIDENTIAL
 CODE R313 AND PLEASE SHOW A LAYOUT FOR
 ALL EXISTING BEDRMS WHICH WILL REQUIER
 ALL SD'S TO BE BROUGHT UP TO THE CURRENT
 CODE PER NFPA-72 11.5.1.1,11.8.3
 PLEASE INDICATE IF THESE ARE GOING TO BE
 NEW OR ARE EXISTING MEETING THE CURRENT
 CODE AND BEING TIED INTO NEW SD'S SHOWN
 ON THESE PLANS.
  
 2) NOTE: PLEASE SEE 210.11C2, 220.16 AS
 THE MIN VA FOR WASHER/LAUNDRY IS NOT
 CORRECT. PLEASE ADJUST.
  
 3) NOTE: PLEASE CORRELATE ALL ELECTRICAL
 HEAT FOR AHU'S WITH MECHANCIAL PLANS.
 PLEASE SEE KW RATINGS DO NOT MATCH. THIS
 WILL AFFECT ELECTRICAL CALCUALATIONS.
 PLEASE ALSO SEE 424.3B FOR MIN OCP
 REQUIRED @125% FOR HEAT STRIPS.
 PLEASE ADJUST CALCULATIONS PER 220.31B.
  
 4) NOTE: PLEASE SEE MANY GEN LIGHTING
 CIRCUITS ARE BEING SHOWN WITH A LOAD OF
 1500 VA ON 15A CIRCUITS, HOWEVER SHOWS
 #12?? PLEASE KNOW, A MAX OF 1440VA IS
 PERMITTED ON A 15A CIRCUIT, UNLESS THESE
 ARE INDEED 20A CIRCUITS AS #12 IS
 TYPICALLY FOR 20A CIRCUITS? PLEASE KNOW,
 IF CIRCUIT IS GOING TO BE 20A, THEN A
 PERMITTED LOAD OF 1920VA IS PERMITTED.
 PLEASE CLARIFY AND COORELATE WHICH ONES.
 240.4,310.16, FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY THE AMOUNT OF
 SMALL APPLIANCE CIRCUITS BEING SHOWN??
 PLEASE SEE PANEL SCHEDULE SHOWS ONE SM
 APPL AND ONE GFI APPL, ALTHOUGH THERE
 ARE WHAT SEEMS TO BE SMALL APPL CIRCUITS
 ON 3RD FLR ALONG WITH FRIG. PLEASE SEE
 PANEL SCHEDULE ONLY SHOWS ONE FRIG.
 PLEASE SEE 210.11C1,210.52B1,220.16 AS A
 MIN OF 1500VA IS REQUIRED FOR "EACH" OF
 SMALL APPPLIANCE CIRCUITS PROVIDE AND A
 MIN OF TWO ARE REQUIRED IN KITCHEN ON
 FIRST FLR.
 PLEASE ALSO SEE THAT THE DINING RM
 RECEPTS SHALL ALSO BE FIGURED PER ABOVE
 CODES NOTED. PLEASE ADJUST.
  
 6) NOTE: PLEASE SEE THE FOLLOWING CODES
 SHALL BE SPECIFIED ON PLANS.
 NFPA-70 (NEC) 2002 NAD NFPA-72 2002.
 PLEASE KNOW, PLANS ONLY MENTIONS TO
 NEC.
 106.1.2
  
 7) NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSING RECEPT ALONG WALL IN MASTER
 BEDRM.
 210.52
  
 8) NOTE: PLEASE SEE CIRCUITS ON PANEL
 SCHEDULE SHALL BE SPECIFIC TO RMS AND
 AREAS IN WHICH THEY FEED.
 IE: MASTER BEDRM LTS, LIVING RM RECEPTS
 ETC. IT IS KNOWN, THAT CIRCUITS WILL BE
 REVISED DURING THE CONSTRUCTION PROCESS,
 HOWEVER CIRCUITS SHALL BE SPECIFIC AT
 THIS TIME. 408.4.
 PLEASE ALSO BE SURE TO LIST ALL THE
 REQUIRED ARC FAULT PROTECTED CIRCUITS ON
 PANEL SCHEDULE. 210.12B, 408.4
  
 9) NOTE: PLEASEGO OVER CALCULATIONS,
 AS THE LOAD SHOWN AFTER TAKING THE
 DE-RATINGS SHOWS 190A'S. PLEASE KNOW,
 LOADS FOR A/ C ARE NOT SHOWN AS NEEDED
 AND SHOWN ON MECHANICAL PLANS, ALONG
 WITH MIN SM APPL/DINING LOADS ETC.
 PLEASE SEE 90.8 AS THE CODEREQUIRES
 SPACE FOR FUTURE LOADS ETC.
 ** PLEASE KNOW, IF LOAD EXCEEDS ANY
 FURTHER THAN SHOWN A LARGER SERVICE MAY
 BE REQUIRED. PLEASE CHECK CALCULATIONS
 AS SHOWN.
  
 10) NOTE: PLEASE SHOW THE LOCATION OF
 THE 200A DISCONNECT AS SHOWN ON RISER.
 110.26,240.24
  
 11) NOTE: PLEASE SEE MISSING LT REQUIRED
 FOR AHU(S) ON FIRST FLR PER 210.70.
 PLEASE SEE 3RD FLR AHU MISSING RECEPT IN
 ATTIC AS LT IS SHOWN. 210.63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  