| 2006-06-21 00:00:00 | ******REVISION DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS REVISION: |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION 106 |
| | CONSTRUCTION DOCUMENTS: REVISION |
| | DRAWINGS IN PENCIL UNACCEPTABLE |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.1 |
| | CONSTRUCTION DOCUMENTS: MINIMUM OF 2 |
| | (TWO) DRAWINGS REQUIRED FOR REVISION. |
| | (NOTE: ONLY ONE REVISION DRAWING |
| | SUBMITTED IN PENCIL) |
| | 3. PER FBC-2004 CHAPTER 1 |
| | 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE |
| | BUILDING OFFICIAL.(NOTE: WHERE THE 1" PE |
| | BELOW GRADE IS INDICATED ON THE REVISION |
| | THE TRANSITION TO ABOVE GROUND GALVAN- |
| | IZED NEEDS TO BE INDICATED ON REVISION) |
| | 4. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.(NOTE: THERE ARE NO |
| | CORRESPONDING LENGTHS INDICATED ON THE |
| | REVISION DRAWING) |
| | 5. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, AND ALL PIPE SIZES.(NOTE: THE |
| | ONLY MATERIAL INDICATED ON REVISION IS |
| | THE UNDERGROUND PE, THE ABOVE GROUND |
| | GALVANIZED MATERIAL NEEDS TO BE |
| | INDICATED ON REVISION DRAWING) |
| | 6. PER FBC-2004 FUEL GAS, SECTION 409.4. |
| | A LISTED SHUT OFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP |
| | REGULATOR. PLEASE SEE CORRECTED REVISION |
| | DRAWING FOR REFERENCE FOR RESUBMITTAL. |
| | 7. FBC-2004 FUEL GAS SEC. 404.12 OUTLET |
| | CLOSURES: GAS OUTLETS THAT DO NOT CON- |
| | NECT TO APPLIANCES SHALL BE CAPPED GAS |
| | TIGHT.(NOTE: ON 2LB SYSTEMS SHUT OFF |
| | VALVE AND REGULATOR SHALL BE INSTALLED |
| | ON FUTURE APPLIANCES FOR FINAL, PLEASE |
| | SEE CORRECTED DRAWING FOR REFERENCE FOR |
| | RESUBMITTAL) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |