| Plan Review Notes For Permit 05110980 |
| Permit Number |
05110980 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-21 00:00:00 | | | | | | | DENIED | | | | | | 1) SPECIFY THE VALLEY TRUSS TIE DOWN | | | CONNECTOR TO MEET THE UPLIFT VALUES | | | STATED ON THE TRUSS PLAN | | | | | | 2) WIND LOAD PROVISIONS TO THE 2004 FBC | | | ARE IN SECTION 1609 NOT 1606 AS | | | SPECIFIED | | | | | | 3) THE VENT SCREENS FROM DRAWING | | | X-SECTION ARE NOW UNDER SECTION 1203.2 | | | OF THE FBC. THEIR ARE SOME CHANGES TO | | | THIS SECTION | | | | | | 4) SPECIFY ATTIC ACCESS SIZE TO MEET | | | 1209.2 FBC. | | | | | | 5) CONSRTUCTION DOCUMENTS SHALL SHOW | | | ROOF & FLOOR LIVE LOADS PER 1603.1 FBC | | | | | | 6) 2 COPIES OF THE STATE OF FLORIDA | | | PRODUCT APPROVAL (COVER SHEET WITH FL#) | | | SHALL BE SUBMITTED WITH THE PRODUCT | | | NOA'S | | | | | | 7) ALL NOA'S SHALL BE MARKED (HILIGHTED) | | | TO CLEARLY SHOW THE INSTALLATION METHOD | | | AND ANY INFORMATION NEEDED PER THE | | | GENERAL LIMITATIONS OF THE PRODUCT, SUCH | | | AS ENHANCED FASTENING FOR WIND LOADS | | | | | | 8) ATTACHED GARAGES REQUIRE A RADON FEE | | | TO BE COLLECTED PER CHAPTER 10D-91, OF | | | THE FLORIDA ADMINISTRATION CODE | | | 10D-91.1313 AND 10D-91.1314 | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | |
|