| Plan Review Notes For Permit 05110892 |
| Permit Number |
05110892 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-02-08 00:00:00 | | | | | | | ** SERVICE REVISED FOR THE THIRD TIME, | | | NOW DOES NOT SHOW ANY MAIN DISCONECTS | | | OUTDSIDE, THIS IS OK, HOWEVER AN | | | "EQUIPMENT GROUNDING CONDUCTOR" IS STILL | | | SHOWN FROM METER TO THE MAIN BRKR PANELS | | | . | | | PLEASE SEE 250.6,250.24, "EQUIPMENT | | | GROUNDING CONDUCTORS" ARE ONLY INSTALLED | | | "AFTER" THE FIRST MEANS OF DISCONNECT. | | | ** PLEASE KNOW, THIS WAS REDLINED ON | | | PLANS AND NO NEED FOR CORRECTIONS OR | | | CHANGES ARE NEEDED AT THIS TIME. | | | PLEASE MAKE THIS CORRECTION IF PLANS ARE | | | SUBMITTED IN FOR REVISIONS BEFORE ROUGH | | | ELECTRICAL INSPECTION. |
|