| 2005-12-12 00:00:00 | ******** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE MIN OCP FOR POOL HEAT |
| | PUMP SHALL BE SIZED AT 125%. 680.9 |
| | |
| | 2)NOTE: PLEASE SEE THE LOAD ON POOL |
| | PANEL EXCEEDS THE 60A OCP FEEDING THIS |
| | PANEL. PLEASE SEE POOL PANEL AND FEEDERS |
| | ARE ALREADY SHOWN AS 100A? |
| | PLEASE CORRELATE. |
| | 240.4,215.5 |
| | |
| | 3)NOTE: PLEASE SEER MISSING HALLWAY |
| | RECEPT PER 210.52H |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. PLEASE SEE ONE SET OF PLANS HAVE |
| | BEEN REDLINED WITH MANY OF THESE |
| | LOCATIONS INDICATED. |
| | |
| | 5)NOTE: PLEASE SEE PLANS DO NOT SEEM TO |
| | INDICATE THE POOL PANEL. PLEASE SHOW. |
| | 215.5 |
| | |
| | 6)NOTE:PLEASE SEE MISSING GFI IN CABANA |
| | BATH AS REQUIRED PER 210.52D, 210.11C3, |
| | 210.8A1 |
| | |
| | 7)NOTE: PLEASE CORRELATE THE # OF GDO |
| | CIRCUITS ON PANEL SCHEDULE WITH THE |
| | ACTUAL # NEEDED ON PLANS. PLEASE SEE |
| | OTHER GARAGE. THREE GDO'S ON PLANS AND |
| | ONLY TWO CIRCUITS ON PANEL SCHEDULE. |
| | |
| | 215.5, 430.24. TABLES). |
| | |
| | 8)NOTE: PLEASE SEE DISC'S FOR A/C CU |
| | UNITS SHALL MEET 110.26 |
| | |
| | 9)NOTE: PLEASE SEE NFPA -72 11-8.3.5 |
| | WHICH REQUIRES ALL SD'S TO BE INSTALLED |
| | WITH-IN 12" OF A FLAT CEILING AREA. |
| | PLEASE SEE "TRAY" CEILING AREA WOULD |
| | REQUIRE TO THESE SD'S LOCATED AT THESE |
| | AREAS IF THEY ARE 12" OR MORE HIGHER |
| | THAN |
| | SURROUNDING CEILING AREA. SEE REDLINED |
| | PLANS. |
| | |
| | |
| | 10)NOTE: PLEASE SEE MIN OCP FOR AHU #1 |
| | IS BE SIZED AT 125% PER 424.3B. |
| | |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM PLANS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. |
| | ONE COPYOF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER REVIEWS WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | |