2005-12-12 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE MIN OCP FOR POOL HEAT
 PUMP SHALL BE SIZED AT 125%. 680.9
  
 2)NOTE: PLEASE SEE THE LOAD ON POOL
 PANEL EXCEEDS THE 60A OCP FEEDING THIS
 PANEL. PLEASE SEE POOL PANEL AND FEEDERS
 ARE ALREADY SHOWN AS 100A?
 PLEASE CORRELATE.
 240.4,215.5
  
 3)NOTE: PLEASE SEER MISSING HALLWAY
 RECEPT PER 210.52H
  
 4)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE ONE SET OF PLANS HAVE
 BEEN REDLINED WITH MANY OF THESE
 LOCATIONS INDICATED.
  
 5)NOTE: PLEASE SEE PLANS DO NOT SEEM TO
 INDICATE THE POOL PANEL. PLEASE SHOW.
 215.5
  
 6)NOTE:PLEASE SEE MISSING GFI IN CABANA
 BATH AS REQUIRED PER 210.52D, 210.11C3,
 210.8A1
  
 7)NOTE: PLEASE CORRELATE THE # OF GDO
 CIRCUITS ON PANEL SCHEDULE WITH THE
 ACTUAL # NEEDED ON PLANS. PLEASE SEE
 OTHER GARAGE. THREE GDO'S ON PLANS AND
 ONLY TWO CIRCUITS ON PANEL SCHEDULE.
  
 215.5, 430.24. TABLES).
  
 8)NOTE: PLEASE SEE DISC'S FOR A/C CU
 UNITS SHALL MEET 110.26
  
 9)NOTE: PLEASE SEE NFPA -72 11-8.3.5
 WHICH REQUIRES ALL SD'S TO BE INSTALLED
 WITH-IN 12" OF A FLAT CEILING AREA.
 PLEASE SEE "TRAY" CEILING AREA WOULD
 REQUIRE TO THESE SD'S LOCATED AT THESE
 AREAS IF THEY ARE 12" OR MORE HIGHER
 THAN
 SURROUNDING CEILING AREA. SEE REDLINED
 PLANS.
  
  
 10)NOTE: PLEASE SEE MIN OCP FOR AHU #1
 IS BE SIZED AT 125% PER 424.3B.
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM PLANS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 ONE COPYOF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWS WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved