Notes
Date Text
2006-06-08 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE CORRELATE PANEL
 SCHEDULES AND RISER SUBMITTED.
 PLEASE SEE THE MDP STILL IS SHOWN
 WITHOUT A MCB AS REQUIRED AND REDLINED
 ON ALL PREVIOUS PLANS.
 PLEASE SEE THE RISER NOW SHOWS WHAT
 APPEARS TO BE A NEW 1200 CB MAIN,
 HOWEVER IS SHOWN AS EXISTING, YET THIS
 WAS NOT SHOWN ON ANY OF THE PREVIOUS
 PLANS AND HAS NOT BEEN REVISED UNDER THE
 MAIN BUILDING PLANS AS OF THIS REVIEW.
 PLEASE ALSO SEE THIS MAIN 1/1 DOES NOT
 INDICATE ANY FEEDERS TO THE MLO MDP.
 215.5, 230.70 ETC
  
 2) NOTE: PLEASE KNOW IT SHALL BE
 CONFIRMED WITH BUILDING REVIEWER, BUT
 THE TRASH COMPACTOR MAY BE REQUIRED TO
 BE UNDER A SEPARATE PERMIT.
 THIS WILL BE CONFIRMED ON 6/13 PLEASE
 KNOW, IF THIS IS THE SITUATION, THEN A
 PERMIT AND PLANS MUST BE ISSUED FIRST.
 PLEASE KNOW IF NOT THEN PLEASE BE SURE
 TO REVISED BASE BUILDING PLANS FOR THE
 ABOVE COMMENTS BEFORE SUBMITTING
 REVISIONS FOR THE SITE PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]