| Plan Review Notes For Permit 05110890 |
| Permit Number |
05110890 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-06-08 00:00:00 | **** UNSAT **** | | | | | | 1) NOTE: PLEASE CORRELATE PANEL | | | SCHEDULES AND RISER SUBMITTED. | | | PLEASE SEE THE MDP STILL IS SHOWN | | | WITHOUT A MCB AS REQUIRED AND REDLINED | | | ON ALL PREVIOUS PLANS. | | | PLEASE SEE THE RISER NOW SHOWS WHAT | | | APPEARS TO BE A NEW 1200 CB MAIN, | | | HOWEVER IS SHOWN AS EXISTING, YET THIS | | | WAS NOT SHOWN ON ANY OF THE PREVIOUS | | | PLANS AND HAS NOT BEEN REVISED UNDER THE | | | MAIN BUILDING PLANS AS OF THIS REVIEW. | | | PLEASE ALSO SEE THIS MAIN 1/1 DOES NOT | | | INDICATE ANY FEEDERS TO THE MLO MDP. | | | 215.5, 230.70 ETC | | | | | | 2) NOTE: PLEASE KNOW IT SHALL BE | | | CONFIRMED WITH BUILDING REVIEWER, BUT | | | THE TRASH COMPACTOR MAY BE REQUIRED TO | | | BE UNDER A SEPARATE PERMIT. | | | THIS WILL BE CONFIRMED ON 6/13 PLEASE | | | KNOW, IF THIS IS THE SITUATION, THEN A | | | PERMIT AND PLANS MUST BE ISSUED FIRST. | | | PLEASE KNOW IF NOT THEN PLEASE BE SURE | | | TO REVISED BASE BUILDING PLANS FOR THE | | | ABOVE COMMENTS BEFORE SUBMITTING | | | REVISIONS FOR THE SITE PLANS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|