Plan Review Notes
Plan Review Notes For Permit 05110890
Permit Number 05110890
Review Stop B
Sequence Number 2
Notes
Date Text
2006-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110890
 ADD: 5400 S DIXIE
 CONT:PLAN REVIEW ONLY
 TEL: (954)816-3351
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS TIE DOWNS- MISSING THE FL
 COVERSHEET
  
 B)PRE FABRICATED CANOPIES- NOT COVERED
 UNDER THIS PERMIT- NO INFORMATION
 SUBMITTED FOR ENGINEERED SYSTEM.
 C) METAL ROOF NON-STRUCTURAL SEE
 SUBMITTAL SHEET. FLORIDA COVERSHEET
 SUBMITTED WITH THE WRONG BACK UP
 DOCUMENTATION.
 D) BAHAMA SHUTTERS- DECORATIVE ,NOA NOT
 REQUIRED BUT ENGINEERING IS REQUIRED TO
 ENSURE THIS SHUTTER WILL NOT ITSELF
 BECOME A MISSLE IN A HIGH WIND EVENT.
 THIS SHUTTER IS TO REMAIN FIXED IN THE
 OPEN POSITION, NEVER TESTED FOR WIND,
 PROVIDE ENGINEERING INDICATING SHUTTER
 ATTACHMENT TO THE BUILDING FIXED IN THE
 OPEN POSITION FOR 140 MPH.
  
  
 2) THE PRE FABRICATED CANOPY SHOULD
 HIGHLIGHT WHAT SYSTEM TO BE USED. PLANS
 INDICATE FOOTERS BUT THE COLUMNS BY
 OTHERS, DOES THIS MEAN THAT THE COLUMNS
 WILL BE BOLTED TO THE TOP OF THE FOOTER.
 NO PLANS SUBMITTED CANOPY TO BE
 CONSIDERED A SEPERATE PERMIT.
  
 3)COMPLIED.
  
 4) SEE COMMENT 1D
  
 5)COMPLIED.
 NEW COMMENTS
 6) SUBMITTAL PRECAST LIGHT POLES ARE A
 ENGINEERED SYSTEM, REQUIES SEALED PLANS.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 05110890
 ADD: 5400 S DIXIE
 CONT:PLAN REVIEW ONLY
 TEL: (954)816-3351
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) TRUSS TIE DOWNS ARE MISSING THE
 FLORIDA COVER SHEET.
  
 B) PRE FABRICATED CANOPIES- TRUE THEY DO
 NOT REQUIRE FL PRODUCT APPROVAL, THEY DO
 REQUIRE ENGINEERED DRAWINGS AND ARE NOT
 COVERED UNDER THIS PERMIT BUT A SEPERATE
 PERMIT.
  
 C) METAL ROOF NON-STRUCTURAL. THE
 FLORIDA COVERSHEET SUBMITTED INDICATES
 THE NOA THAT TIES TO THIS REPORT. A
 DIFFERENT NOA WAS SUBMITTED.
  
 D) BAHAMA SHUTTERS- SEE COMMENT# 4.
  
 2) THE PRE FABRICATED CANOPY SHOULD
 HIGHLIGHT WHAT SYSTEM TO BE USED. PLANS
 INDICATE FOOTERS BUT THE COLUMNS BY
 OTHERS, DOES THIS MEAN THAT THE COLUMNS
 WILL BE BOLTED TO THE TOP OF THE FOOTER?
 THIS WAS THE FIRST SET OF COMMENTS , NO
 ENGINEERING WAS SUBMITTED. A SEPERATE
 PERMIT IS REQUIRED FOR AWNINGS AND
 CANOPIES.
  
 3) COMPLIED.
  
 4) THE BAHAMA STYLE SHUTTERS DO NOT NEED
 STATE APPROVAL BUT THAT THE INSTALLATION
 WILL BE FOR A FIXED OPEN POSITION DURING
 A HIGH WIND EVENT. THIS TYPE OF
 INSTALLATION WILL REQUIRE ENGINEERING
 FOR THE INSTALLATION OF THE BAHAMA
 SHUTTER INSTALLED AS A FIXED SHUTTER IN
 THE OPEN POSITION. MUST MEET THE 140 MPH
 TO NOT BECOME A MISSLE ITSELF.
  
 5)COMPLIED.
  
 NEW COMMENT.
 6) SITE LIGHT POLES ARE AN ENGINEERED
 SYSTEM REQUIRING SEALED PLANS.
 RC ENGINEERING.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  