| Plan Review Notes For Permit 05110890 |
| Permit Number |
05110890 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-24 00:00:00 | **** UNSAT **** | | | | | | ** PLEASE KNOW, PLANS HAVE ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW" ONLY AND NOT | | | FOR PERMIT. | | | | | | 1)NOTE: PLEASE SUBMIT THE SITE LIGHTING | | | POLES/FIXTURES CALCULATIONS AT THIS | | | TIME. | | | THIS WILL BE REVIEWED BY BLDG REVIEW. | | | | | | 2)NOTE: PLEASE SE BLDG NOTES AS SEALED | | | SURVEY IS A PHOTOCPOY THE SURVEYOR'S | | | ORIGINAL SIGNATURE. PLEASE SEE FS | | | 472.025 WHICH REQUIRES AN ORIGINAL | | | SIGNATURE. | | | | | | 3)NOTE: PLEASE SEE PANEL "PA", PLEASE BE | | | SURE TO CORRELATE WITH MAIN PLANS. | | | PLEASE SEE PLANS MENTIONS, NO CHANGES TO | | | LOAD, HOWEVER THIS CAN NOT BE POSSIBLE | | | AS THESE NEW ELECTRICAL ITEMS DO NOT | | | EXIST AT THIS TIME. | | | PLEASE SEE NOTES UNDER MAIN PERMIT. | | | | | | 4)NOTE: PLEASE SEE NEW ELECTRICAL | | | LIGHTING SHOWN ON A-SHEETS WHICH IS NOT | | | ON PLANS. PLEASE ALSO VERIFY WITH PLANS | | | UNDER MAIN PERMIT WHICH DO NOT SEEM TO | | | SHOW THESE. | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW . IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|