Date Text
2005-12-24 00:00:00**** UNSAT ****
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND NOT
 FOR PERMIT.
  
 1)NOTE: PLEASE SUBMIT THE SITE LIGHTING
 POLES/FIXTURES CALCULATIONS AT THIS
 TIME.
 THIS WILL BE REVIEWED BY BLDG REVIEW.
  
 2)NOTE: PLEASE SE BLDG NOTES AS SEALED
 SURVEY IS A PHOTOCPOY THE SURVEYOR'S
 ORIGINAL SIGNATURE. PLEASE SEE FS
 472.025 WHICH REQUIRES AN ORIGINAL
 SIGNATURE.
  
 3)NOTE: PLEASE SEE PANEL "PA", PLEASE BE
 SURE TO CORRELATE WITH MAIN PLANS.
 PLEASE SEE PLANS MENTIONS, NO CHANGES TO
 LOAD, HOWEVER THIS CAN NOT BE POSSIBLE
 AS THESE NEW ELECTRICAL ITEMS DO NOT
 EXIST AT THIS TIME.
 PLEASE SEE NOTES UNDER MAIN PERMIT.
  
 4)NOTE: PLEASE SEE NEW ELECTRICAL
 LIGHTING SHOWN ON A-SHEETS WHICH IS NOT
 ON PLANS. PLEASE ALSO VERIFY WITH PLANS
 UNDER MAIN PERMIT WHICH DO NOT SEEM TO
 SHOW THESE.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]