Plan Review Notes
Plan Review Notes For Permit 05110873
Permit Number 05110873
Review Stop Z
Sequence Number 6
Notes
Date Text
2007-07-23 17:02:08AMY STELLY
 URBAN DESIGN
 822-1440
  
 PLEASE REVISE THE CURRENT DRAWINGS AND PROVIDE
 ADDITIONAL DRAWINGS AS NECESSARY TO REFLECT THE
 FOLLOWING COMMENTS FROM BRIAN COLLINS:
  
 1.NEED ADVANCE CROSSING SIGNAGE - S1-1 PLUS W16-9P
 (FYG - RETROREFLECTIVE) BOTH NORTH AND SOUTH
 2.SHOW CROSSING SIGNAGE ON NB FLAGLER
 3.SHOW DETAILS FOR ALL SIGNS
 4.STAMPED CONCRETE OR PAVER BRICKS SHOULD BE USED TO
 FILL MEDIAN.
 5.EUROPEAN CROSSWALK DETAIL SHOULD REFLECT FLAGLER
 CROSS SECTION, MEDIAN, AND YIELD LINE NOT STOP BAR.
 6.CROSSWALK ON PLANS DOES NOT SHOW IN-GROUND LIGHTS
 7.BLOW -UP OF CROSSWALK DETAIL AND IN-GROUND LIGHTS
 SHOULD BE PROVIDED
 8.SINCE THERE IS ADDITIONAL LANE WIDTH DUE TO REMOVAL
 OF LTL LANE AT 1 WATERMARK, EXTEND MEDIAN 30 FT. TO
 SOUTH.THIS WOULD HELP DETER ILLEGAL LEFTS FROM THE
 NEW PARKING AREA ON THE EAST SIDE OF FLAGLER.
 9.MEDIAN NORTH OF CROSSWALK MAY BE REDUCED FROM 35 TO
 20FT.TO ALLOW ACCESS TO YACHT CLUB AND PARKING AREA.
 10.TRAFFIC SEPARATORS DETAILS ARE A LITTLE TOUGH TO
 READ.
 11.ADD NO U-TURN SIGNAGE (R3-4) AT NORTH AND SOUTH
 ENDS OF ISLAND.
 12.TEMPORARY PAVEMENT MARKINGS SHALL BE INSTALLED
 AFTER THE FINAL LIFT OF ASPHALT IS COMPLETED UNTIL THE
 PERMANENT (THERMOPLASTIC) MARKINGS ARE INSTALLED.
  