2007-04-14 12:41:54** UNSAT **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE TO
 CHANGES IN PLANS AND NEW RISER NOW SHOWN WHICH WAS NOT
 ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON
 TITLE BLOCKS FOR THE FOLLOWING AS REQUIRED UNDER FAC
 61G1-16.004,FAC 61G15-23.002 -FS 481.219, FS 481.319,
 471.023.
 THESE ITEMS ARE REQUIRED WHETHER OR NOT SHEETS WERE
 STAMPED BY OTHER REVIEWERS OR OTHER TRADES OR COMMENTS
 WERE MADE BY OTHER TRADES OR REVIEWER(S).
 A) PLEASE SEE MISSING INFORMATION FOR ICON DESIGN
 GROUP, WHICH IS MISSING THE PRINTED NAME, PRINTED
 LICENSE NUMBER OF THE DESIGNER OF RECORD. PLEASE ALSO
 SEE THE MISSING LICENSE NUMBERS FOR THE FIRM FOR
 PRACTICING ARCHITECTURAL AND ENGINEERING SERVICE.
 SEE SECTIONS ABOVE OR CONTACT THE STATE OF FLORIDA
 LEGAL COUNSEL TO THE BOARD OF ARCHITECTS AND THE
 FLORIDA BOARD OF ENGINEERS FOR ANY OTHER QUESTIONS.
 B) PLEASE SEE THE SHEETS FOR ENVIRONMENTAL DESIGN GROUP
 WHICH IS MISSING THE FIRM LICENSE NUMBER WHICH IS
 REQUIRED TO BE PRINTED ON THE TITLE BLOCKS. THE SHEETS
 WHICH CONTAINED STAMPS HAVE SINCE BEEN *VOIDED* AS
 THESE SHEETS WILL BE REQUIRED TO BE REVISED TO
 COORDINATE WITH ELECTRICAL PLANS, SEE OTHER COMMENTS.
  
 2) NOTE: PLEASE SEE THE WIND LOAD CALCULATIONS WHICH
 WERE SUBMITTED ARE NOT SIGNED, DATED, SEALED OR
 CONTAINS ANY DESIGNER OF RECORD OR ENGINEERING TITLE
 BLOCK INFORMATION AS REQUIRED.
 PLEASE SEE BUILDING REVIEW COMMENTS FOR THIS ALSO.
 FBC 106.1.2
 FS 471.025, 471.023, FAC 61G15-23.002
  
 3) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE.
 PLEASE SEE PANEL SCHEDULE SHOW THE PANEL AS A 125AMP
 MLO, WHERE RISER INDICATES A 60MCB PANEL?
 PLEASE KNOW IF THIS BREAKER IS GOING TO BE A *BACK-FED*
 DEVICE, THEN THE PANEL SCHEDULE WILL INDICATE WHICH
 SPACE THIS WILL BE LOCATED AND SHALL ALSO INDICATE THE
 REQUIRED REJECTION TYPE DEVICE REQUIRED.
 PLEASE BE SURE TO VERIFY THE AIC RATING FOR
 BACK-FEEDING A BRANCH BREAKER AND DISTANCE FROM FPL.
 110.9, 230,
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE PANEL INDICATES LOCATION TO BE
 AT *MARINA* WHICH IS ACTUALLY NOT PART OF THIS LEGAL
 PROPERTY. PLEASE CLARIFY.
 PLEASE ALSO SEE THE SHEETS 1/2 AND 2/2 WHICH ARE DONE
 BY ENVIRONMENTAL DESIGN GROUP NEED TO BE COORDINATED
 WITH THE ELECTRICAL SHEETS INDICATE ALL EQUIPMENT,
 LIGHTING ETC.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY AFFECT
 ANY OTHER SHEETS OR PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved