| Date |
Text |
| 2007-04-14 12:41:54 | ** UNSAT ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE TO |
| | CHANGES IN PLANS AND NEW RISER NOW SHOWN WHICH WAS NOT |
| | ON PREVIOUS PLANS. |
| | |
| | 1) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON |
| | TITLE BLOCKS FOR THE FOLLOWING AS REQUIRED UNDER FAC |
| | 61G1-16.004,FAC 61G15-23.002 -FS 481.219, FS 481.319, |
| | 471.023. |
| | THESE ITEMS ARE REQUIRED WHETHER OR NOT SHEETS WERE |
| | STAMPED BY OTHER REVIEWERS OR OTHER TRADES OR COMMENTS |
| | WERE MADE BY OTHER TRADES OR REVIEWER(S). |
| | A) PLEASE SEE MISSING INFORMATION FOR ICON DESIGN |
| | GROUP, WHICH IS MISSING THE PRINTED NAME, PRINTED |
| | LICENSE NUMBER OF THE DESIGNER OF RECORD. PLEASE ALSO |
| | SEE THE MISSING LICENSE NUMBERS FOR THE FIRM FOR |
| | PRACTICING ARCHITECTURAL AND ENGINEERING SERVICE. |
| | SEE SECTIONS ABOVE OR CONTACT THE STATE OF FLORIDA |
| | LEGAL COUNSEL TO THE BOARD OF ARCHITECTS AND THE |
| | FLORIDA BOARD OF ENGINEERS FOR ANY OTHER QUESTIONS. |
| | B) PLEASE SEE THE SHEETS FOR ENVIRONMENTAL DESIGN GROUP |
| | WHICH IS MISSING THE FIRM LICENSE NUMBER WHICH IS |
| | REQUIRED TO BE PRINTED ON THE TITLE BLOCKS. THE SHEETS |
| | WHICH CONTAINED STAMPS HAVE SINCE BEEN *VOIDED* AS |
| | THESE SHEETS WILL BE REQUIRED TO BE REVISED TO |
| | COORDINATE WITH ELECTRICAL PLANS, SEE OTHER COMMENTS. |
| | |
| | 2) NOTE: PLEASE SEE THE WIND LOAD CALCULATIONS WHICH |
| | WERE SUBMITTED ARE NOT SIGNED, DATED, SEALED OR |
| | CONTAINS ANY DESIGNER OF RECORD OR ENGINEERING TITLE |
| | BLOCK INFORMATION AS REQUIRED. |
| | PLEASE SEE BUILDING REVIEW COMMENTS FOR THIS ALSO. |
| | FBC 106.1.2 |
| | FS 471.025, 471.023, FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE. |
| | PLEASE SEE PANEL SCHEDULE SHOW THE PANEL AS A 125AMP |
| | MLO, WHERE RISER INDICATES A 60MCB PANEL? |
| | PLEASE KNOW IF THIS BREAKER IS GOING TO BE A *BACK-FED* |
| | DEVICE, THEN THE PANEL SCHEDULE WILL INDICATE WHICH |
| | SPACE THIS WILL BE LOCATED AND SHALL ALSO INDICATE THE |
| | REQUIRED REJECTION TYPE DEVICE REQUIRED. |
| | PLEASE BE SURE TO VERIFY THE AIC RATING FOR |
| | BACK-FEEDING A BRANCH BREAKER AND DISTANCE FROM FPL. |
| | 110.9, 230, |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE PANEL INDICATES LOCATION TO BE |
| | AT *MARINA* WHICH IS ACTUALLY NOT PART OF THIS LEGAL |
| | PROPERTY. PLEASE CLARIFY. |
| | PLEASE ALSO SEE THE SHEETS 1/2 AND 2/2 WHICH ARE DONE |
| | BY ENVIRONMENTAL DESIGN GROUP NEED TO BE COORDINATED |
| | WITH THE ELECTRICAL SHEETS INDICATE ALL EQUIPMENT, |
| | LIGHTING ETC. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY AFFECT |
| | ANY OTHER SHEETS OR PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |