2007-06-13 13:17:29BUILDING PLAN REVIEW
 PERMIT: 05110873
 ADD: 807 N FLAGLER DR
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) COMMENT # 3 FROM THE PREVIOUS REVIEW DEALS WITH THE
 WIND LOAD INFORMATION REGARDING THE LIGHT POLES. THE
 RESPONSE INDICATES THEY WERE ORDERED FROM THE
 MANUFACTUERER?
 PLEASE PROVIDE THE WIND LOAD CALCULATIONS THAT ARE
 SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER. IT
 APPEARS THAT THE MANUFACTURER MAY BE ACTING AS AN
 ENGINEER?
  
 3) SEE ELECTRICAL COMMENTS IN REGARDS TO EITHER
 LICENSINFG REQUIREMENTS FOR ARCHITECTS OR ENGINEERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  