| Notes |
| Date |
Text |
| 2006-01-04 00:00:00 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE INDICATE THE CIRCUITING | | | ON PLANS AND CORRELATE WITH A PANEL | | | SCHEDULE TO BE SUBMITTED. | | | | | | PLEASE SEE 700.12E FOR CIRCUITING OF | | | EM/EXT LTS. | | | THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | | | | 2)NOTE: PLEASE SEE POSSIBLE FIRE REVIEW | | | COMMENTS AS THE PLANS APPEAR TO SHOW THE | | | SD'S AS 120V HARDWIRED. ARE THESE | | | CONNECTED INTO FA SYSTEM OR PANEL? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|