Notes
Date Text
2006-12-29 17:17:07** PROVISO **
  
 NOTES REDLINED, AND NOTES FOR INFORMATION ****
  
 PLANS ARE TO BE REVISED FOR NOTES #1 AND #2 BELOW
 ALONG WITH ANY OTHER REVISIONS BEFORE ROUGH.
  
  
 *** 1) ELECTRICAL ROOMS, EQUIPMENT ROOMS, PIT AREA AND
 ROOMS OF THE LIKE SHALL CONTAIN AUTOMATIC MEANS FOR
 LIGHTING TO TURN OFF AS REQUIRED PER FBC
 13-415.1.ABC.1.1, .1.2, AND .1.3
 THIS WAS NOT ON ORIGINAL REVIEW , AS THIS WAS NOT KNOWN
 TO THIS OFFICE.
 ** AS INFORMATION FOR FUTURE BUILD OUTS, ALL SHALL
 COMPLY COMPLETELY WITH THE NEW REQUIREMENTS UNDER THE
 NEW 2004 FBC CHAPTER 13.
  
 ** 2) PLEASE SEE THE MINIMUM LEVELS FOR HORN/STROBES
 SHALL MEET 2004 FBC 11-4.28.2, .3(4).
 75 MIN CANDELAS ON STROBES AND 15DB MIN FOR HORNS. THIS
 COMMENT WAS NOT MADE ON ANY PREVIOUS ELECTRICAL REVIEWS
 AS IT HAS NOW ONLY BECOME ONE OF THE ITEMS ELECTRICAL
 PLAN REVIEW WILL BE REQUIRED TO REVIEW FOR.
  
 3) PLEASE SEE THE TRUSS PLANS SUBMITTED STILL DO NOT
 CONTAIN AN ORIGINAL SIGNATURE, THEY ARE IN FACT COLOR
 PHOTO-COPIES. SEE BUILDING REVIEW NOTES OR BE SURE TO
 SUBMIT/CHANGE THESE DOCUMENTS OUT BEFORE BUILDING
 REVIEW COMMENCES
 IF THERE ARE ANY QUESTIONS ON THIS OR WHEN AN
 APPOINTMENT TO DO SO CAN BE SET UP, PLEASE CALL.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESIATE IN
 CONTACTING THIS OFFICE.
  