| Plan Review Notes For Permit 05110803 |
| Permit Number |
05110803 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-12-29 17:17:07 | ** PROVISO ** | | | | | | NOTES REDLINED, AND NOTES FOR INFORMATION **** | | | | | | PLANS ARE TO BE REVISED FOR NOTES #1 AND #2 BELOW | | | ALONG WITH ANY OTHER REVISIONS BEFORE ROUGH. | | | | | | | | | *** 1) ELECTRICAL ROOMS, EQUIPMENT ROOMS, PIT AREA AND | | | ROOMS OF THE LIKE SHALL CONTAIN AUTOMATIC MEANS FOR | | | LIGHTING TO TURN OFF AS REQUIRED PER FBC | | | 13-415.1.ABC.1.1, .1.2, AND .1.3 | | | THIS WAS NOT ON ORIGINAL REVIEW , AS THIS WAS NOT KNOWN | | | TO THIS OFFICE. | | | ** AS INFORMATION FOR FUTURE BUILD OUTS, ALL SHALL | | | COMPLY COMPLETELY WITH THE NEW REQUIREMENTS UNDER THE | | | NEW 2004 FBC CHAPTER 13. | | | | | | ** 2) PLEASE SEE THE MINIMUM LEVELS FOR HORN/STROBES | | | SHALL MEET 2004 FBC 11-4.28.2, .3(4). | | | 75 MIN CANDELAS ON STROBES AND 15DB MIN FOR HORNS. THIS | | | COMMENT WAS NOT MADE ON ANY PREVIOUS ELECTRICAL REVIEWS | | | AS IT HAS NOW ONLY BECOME ONE OF THE ITEMS ELECTRICAL | | | PLAN REVIEW WILL BE REQUIRED TO REVIEW FOR. | | | | | | 3) PLEASE SEE THE TRUSS PLANS SUBMITTED STILL DO NOT | | | CONTAIN AN ORIGINAL SIGNATURE, THEY ARE IN FACT COLOR | | | PHOTO-COPIES. SEE BUILDING REVIEW NOTES OR BE SURE TO | | | SUBMIT/CHANGE THESE DOCUMENTS OUT BEFORE BUILDING | | | REVIEW COMMENCES | | | IF THERE ARE ANY QUESTIONS ON THIS OR WHEN AN | | | APPOINTMENT TO DO SO CAN BE SET UP, PLEASE CALL. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESIATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|