2006-10-02 00:00:0010/02/06 ***FAILED***
  
 1) LOCATION OF A/C UNITS ON THE
 ELECTRICAL PLANS CONFLICTS WITH THE
 INSTALLATION OF LANDSCAPING.A/C UNITS
 SHALL BE SHOWN ON THE SITE AND LANDSCAPE
 PLANS AND SHALL BE ADJUSTED ACCORDINGLY
 TO ACCOMMODATE SUCH INSTALLATIONS.
 ADDITIONALLY, ENSURE THAT THE MECHANICAL
 EQUIPMENT DOES NOT ENCROACH MORE THAN 3
 FEET INTO A REQUIRED SETBACK.
  
 2) THE SITE PLAN INDICATES 45,000 GROSS
 SQUARE FEET OF BUILDING WHILE THE ARCH.
 PLANS INDICATE 58,998 GROSS SQUARE FEET.
 PLANS SHALL BE CONSISTENT AND THE
 PARKING, LANDSCAPING, PERVIOUS,
 IMPERVIOUS, ETC. SHALL BE ADJUSTED
 ACCORDINGLY.
  
 3) A NOTE SHALL BE PROVIDED ON THE SITE
 AND LANDSCAPE PLANS THAT THE MONUMENT
 WILL BE UNDER A SEPARATE PERMIT.
  