| 2006-09-21 00:00:00 | ***** UNSAT 2ND REVIEW ***** |
| | |
| | BLGD "B". |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS, |
| | SOME OF WHICH ARE BEING NOTEDBY THIS |
| | REVIEWER AS A "HEADS-UP". THESE ITEMS |
| | ARE REQUIRED FOR COMPLIANCE FOR THE |
| | ENTIRE PROJECT. |
| | PLEASE SEE MANY ARE NOT FOR THE |
| | ELECTRICAL REVIEW. |
| | PLEASE SEE SOME ITEMS WHICH ARE REQUIRED |
| | FOR ELECTRICAL . |
| | PLEASE SEE ONLY ONE COMMENT FROM |
| | PREVIOUS ELECTRICAL REVIEW STILL STANDS |
| | AND SOME NEW COMMENTS BASED ON PLANS |
| | SUBMITTED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING FOOTER STEEL |
| | REQUIRED TO BE PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. 250.50 |
| | PLEASE SEE CWP, GRND RODS AND BLDG STEEL |
| | IS BEING SHOWN, ONLY MISSING FOOTER |
| | STEEL. |
| | |
| | 2) NOTE: PLEASE SEE FA SHEETS SUBMITTED |
| | SEPARATELY FROM SETS WHICH ARE NOT |
| | SIGNED , DATED OR SEALED BY THE ENGINEER |
| | OF RECORD. PLEASE ALSO SEE SHEETS |
| | WITHOUT TITLE BLOCKS. |
| | PLEASE SEE FBC 106.1 FOR MINIMUM |
| | REQUIRMENTS FOR PLANS/DRAWINGS TO BE |
| | SUBMITTED. (SCALE/CLARITY ETC) |
| | FS 471.025 |
| | |
| | 3) NOTE: PLEASE SEE ALL FIRE SPRINKLER |
| | PLANS WHICH CONTAIN A "RUBBER STAMP" FOR |
| | THE ENGINEER OF RECORD. PLEASE KNOW, |
| | THIS HAS BEEN NOTED ON OTHER PROJECTS |
| | FOR THE SAME ENGINEER THAT A "RUBBER |
| | STAMP" FOR THE REQUIRED ORIGINAL |
| | SIGNATURE IS NOT ACCEPTABLE UNDER FAC |
| | 61G15-23.002, FLORIDA STATUES 471.025. |
| | PLEASE ALSO SEE THE SEAL FOR SAID |
| | ENGINEER IS ALSO NO LONGER VALID AS THE |
| | SEAL HAS EXPIRED PER RULING IN THEFAC |
| | 61G15-23.001. THE RULING PASSED IN FEB |
| | "04"WHICH REQUIRED THE WORDING OF |
| | "CERTIFICATE" TO CHANGE TO "LICENSE" FOR |
| | ALL ENGINEERS. PLEASE KNOW THE STATE |
| | FBPE'S HAD ANEXTENSIONGRANTED FOR |
| | ALMOST TWO YEARS TO GIVE ALL ENGINEERS |
| | TIME TO OBTAIN THEIR NEW SEALS. THIS |
| | EXTENED DATE WAS TO DEC 31ST, 2005. |
| | PLEASE KNOW AS THIS HAS BEEN STATED ON |
| | PREVIOUS PROJECTS AND PLANS ARE STILL |
| | COMING IN WITH A "RUBBER STAMP" FROM |
| | THIS DESIGN PROFESSIOAL, ONE SET OF EACH |
| | PLAN FOR EACH SET AND EACHBUILDING IS |
| | NOW BEING RETAINED BY THIS OFFICE FOR |
| | FILE. PLEASE KNOW THIS MAY BE TURNED |
| | OVER TO THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS FOR REVIEW AND |
| | STATE'S LEGAL COUNSEL TO THE BOARD. |
| | |
| | 4) NOTE: PLEASE SEE TRUSS PLANS. PLEASE |
| | SEE BUILDING REVIEW COMMENTS. |
| | A)PLEASE SEE THE FAC 61G15-23.001. THE |
| | RULING PASSED IN FEB "04" REQUIRED THE |
| | WORDING OF "CERTIFICATE" TO CHANGE TO |
| | "LICENSE" FOR ALL ENGINEERS. PLEASE KNOW |
| | THE STATE FBPE'S HAD ANEXTENSION TO |
| | DEC 31ST, 2005. PLEASE OBTAIN NEW SEAL. |
| | B) PLEASE ALSO SEE THAT THESE SHEETS |
| | ALSO DO NOT CONTAIN AN ORIGINAL |
| | SIGNATURE AS REQUIRED UNDER FS 471.025, |
| | FAC 61G15-23.002. |
| | THESE MAY ALSO BE RETAINED. |
| | |
| | 5) NOTE: PLEASE SEE SETS OF PLANS FOR |
| | THE "EPICORE FRAMING PLAN". PLEASE SEE |
| | THESE CONTAIN A RAISED SEAL OVER |
| | SIGNATURES WHICH ARENOT ORIGINAL AND |
| | ARE "PHOTO-COPIES" OF THE ENGINEER'S |
| | SIGNATURE WHICH IS REQUIRED TO BE |
| | ORIGINAL. |
| | PLEASE KNOW THESE ALSO MAY BE RETAINED |
| | AS ALL SETS FOR BOTH BLDG'S ARE THE SAME |
| | AS NOTED. |
| | |
| | 6) NOTE: PLEASE SEE SURVEY'S , PLEASE |
| | SEE THESE ALSO CONTAIN A RAISED SEAL |
| | OVER A "COPIED" SIGNATURE WHICH IS NOT |
| | PERMITTED UNDER FAC 61G17 AND FS |
| | 472.025. |
| | PLEASE BE SURE THESE ARE SIGNED WITH |
| | ORIGINAL SIGNATURE. |
| | |
| | ** PLEASE SEE THE COMMENTS FOR THE |
| | ELECTRICAL ENGINEERING FIRM ARE MINOR |
| | EXCEPT FOR THE FA SHEETS. |
| | |
| | ** PLEASE KNOW, THE SIGNING, DATING AND |
| | SEALING OF ALL DOCUMENTS IS MOST |
| | IMPORTANT!! |
| | |
| | ** IMPORTANT** |
| | |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | PLEASE SEE COMPLETE SETS WITH ALL |
| | ARCHITECTURAL PLANS WERE NOT MADE INTO |
| | THE SETS SUBMITTED. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |