Plan Review Notes
Plan Review Notes For Permit 05110803
Permit Number 05110803
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-21 00:00:00***** UNSAT 2ND REVIEW *****
  
 BLGD "B".
  
 ** PLEASE SEE THE FOLLOWING COMMENTS,
 SOME OF WHICH ARE BEING NOTEDBY THIS
 REVIEWER AS A "HEADS-UP". THESE ITEMS
 ARE REQUIRED FOR COMPLIANCE FOR THE
 ENTIRE PROJECT.
 PLEASE SEE MANY ARE NOT FOR THE
 ELECTRICAL REVIEW.
 PLEASE SEE SOME ITEMS WHICH ARE REQUIRED
 FOR ELECTRICAL .
 PLEASE SEE ONLY ONE COMMENT FROM
 PREVIOUS ELECTRICAL REVIEW STILL STANDS
 AND SOME NEW COMMENTS BASED ON PLANS
 SUBMITTED.
  
  
 1) NOTE: PLEASE SEE MISSING FOOTER STEEL
 REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
 PLEASE SEE CWP, GRND RODS AND BLDG STEEL
 IS BEING SHOWN, ONLY MISSING FOOTER
 STEEL.
  
 2) NOTE: PLEASE SEE FA SHEETS SUBMITTED
 SEPARATELY FROM SETS WHICH ARE NOT
 SIGNED , DATED OR SEALED BY THE ENGINEER
 OF RECORD. PLEASE ALSO SEE SHEETS
 WITHOUT TITLE BLOCKS.
 PLEASE SEE FBC 106.1 FOR MINIMUM
 REQUIRMENTS FOR PLANS/DRAWINGS TO BE
 SUBMITTED. (SCALE/CLARITY ETC)
 FS 471.025
  
 3) NOTE: PLEASE SEE ALL FIRE SPRINKLER
 PLANS WHICH CONTAIN A "RUBBER STAMP" FOR
 THE ENGINEER OF RECORD. PLEASE KNOW,
 THIS HAS BEEN NOTED ON OTHER PROJECTS
 FOR THE SAME ENGINEER THAT A "RUBBER
 STAMP" FOR THE REQUIRED ORIGINAL
 SIGNATURE IS NOT ACCEPTABLE UNDER FAC
 61G15-23.002, FLORIDA STATUES 471.025.
 PLEASE ALSO SEE THE SEAL FOR SAID
 ENGINEER IS ALSO NO LONGER VALID AS THE
 SEAL HAS EXPIRED PER RULING IN THEFAC
 61G15-23.001. THE RULING PASSED IN FEB
 "04"WHICH REQUIRED THE WORDING OF
 "CERTIFICATE" TO CHANGE TO "LICENSE" FOR
 ALL ENGINEERS. PLEASE KNOW THE STATE
 FBPE'S HAD ANEXTENSIONGRANTED FOR
 ALMOST TWO YEARS TO GIVE ALL ENGINEERS
 TIME TO OBTAIN THEIR NEW SEALS. THIS
 EXTENED DATE WAS TO DEC 31ST, 2005.
 PLEASE KNOW AS THIS HAS BEEN STATED ON
 PREVIOUS PROJECTS AND PLANS ARE STILL
 COMING IN WITH A "RUBBER STAMP" FROM
 THIS DESIGN PROFESSIOAL, ONE SET OF EACH
 PLAN FOR EACH SET AND EACHBUILDING IS
 NOW BEING RETAINED BY THIS OFFICE FOR
 FILE. PLEASE KNOW THIS MAY BE TURNED
 OVER TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW AND
 STATE'S LEGAL COUNSEL TO THE BOARD.
  
 4) NOTE: PLEASE SEE TRUSS PLANS. PLEASE
 SEE BUILDING REVIEW COMMENTS.
 A)PLEASE SEE THE FAC 61G15-23.001. THE
 RULING PASSED IN FEB "04" REQUIRED THE
 WORDING OF "CERTIFICATE" TO CHANGE TO
 "LICENSE" FOR ALL ENGINEERS. PLEASE KNOW
 THE STATE FBPE'S HAD ANEXTENSION TO
 DEC 31ST, 2005. PLEASE OBTAIN NEW SEAL.
 B) PLEASE ALSO SEE THAT THESE SHEETS
 ALSO DO NOT CONTAIN AN ORIGINAL
 SIGNATURE AS REQUIRED UNDER FS 471.025,
 FAC 61G15-23.002.
 THESE MAY ALSO BE RETAINED.
  
 5) NOTE: PLEASE SEE SETS OF PLANS FOR
 THE "EPICORE FRAMING PLAN". PLEASE SEE
 THESE CONTAIN A RAISED SEAL OVER
 SIGNATURES WHICH ARENOT ORIGINAL AND
 ARE "PHOTO-COPIES" OF THE ENGINEER'S
 SIGNATURE WHICH IS REQUIRED TO BE
 ORIGINAL.
 PLEASE KNOW THESE ALSO MAY BE RETAINED
 AS ALL SETS FOR BOTH BLDG'S ARE THE SAME
 AS NOTED.
  
 6) NOTE: PLEASE SEE SURVEY'S , PLEASE
 SEE THESE ALSO CONTAIN A RAISED SEAL
 OVER A "COPIED" SIGNATURE WHICH IS NOT
 PERMITTED UNDER FAC 61G17 AND FS
 472.025.
 PLEASE BE SURE THESE ARE SIGNED WITH
 ORIGINAL SIGNATURE.
  
 ** PLEASE SEE THE COMMENTS FOR THE
 ELECTRICAL ENGINEERING FIRM ARE MINOR
 EXCEPT FOR THE FA SHEETS.
  
 ** PLEASE KNOW, THE SIGNING, DATING AND
 SEALING OF ALL DOCUMENTS IS MOST
 IMPORTANT!!
  
 ** IMPORTANT**
  
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 PLEASE SEE COMPLETE SETS WITH ALL
 ARCHITECTURAL PLANS WERE NOT MADE INTO
 THE SETS SUBMITTED.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  