Plan Review Notes
Plan Review Notes For Permit 05110803
Permit Number 05110803
Review Stop B
Sequence Number 2
Notes
Date Text
2006-10-20 06:50:24 
  
 DENIED
  
 1) FIXED WINDOWS APPEAR TO BE SEPERATE LITES IF SO
 MULLIONS ARE REQUIRED AND PRODUCT APPROVALS SHALL BE
 SUBMITTED
  
 2) THE STATE COVER FL#5259 FOR THE POLYSTICK
 UNDERLAYMENT IS NOT THE CORRECT COVER FOR THE
 MIAMI-DADE NOA PLEASE SUBMIT CORRECT COVER (FL#986-R1)
  
 3) THE STATE COVER FL#2795 FOR THE FIXED WINDOWS ARE
 FOR THE 2001 CODE CYCLE, YALE OGRON DOES NOT YET HAVE
 STATE APPROVAL FOR THIS PRODUCT SO A LOCAL PRODUT
 APPROVAL WAS GIVEN FOR THE MIAMI-DADE NOA. THE SAME
 APPLIES TO THE SMITH MOUNTAIN ENTRANCE DOOR & TRANSOM
 NOA'S
  
 4) PROVIDE THE UL LISTING/SYSTEM USED TO MEET THE ONE
 HOUR RATING FOR THE CEILING AND ATTIC ACCESS PANELS.
 DRAWINGS ONLY SHOW ONE LAYER 5/8" TYPE X WHICH IS A 40
 MINUTE RATING
  
 5) PROVIDE ENERGY CALC'S PER 13-101.1.6 FBC USING
 METHOD B AS PER CONVERSATION WITH PATTY KRAUSS (MECH
 PLAN REVEIW) AND SHOW COMPLIANCE ON THE CONSTRUCTION
 DOCUMENTS
  
 6) PER ELEVATOR SHOP DRAWINGS PROVIDE MINIMUM ONE HR
 RATED DOOR TO THE MACHINE ROOM COMPLETE WITH CLOSER AND
 LOCK
  
 7) PROVIDE HARDWARE SCHEDULE WITH HARDWARE THAT MEETS
 THE ACCESSABILITY REQUIREMENTS PER 11-4.13.8 THROUGH
 11-4.13.11
  
 8) PROVIDE SHORING PLANS FOR BEAMS (OTHER THAN TAHT
 ALREADY SUPPLIED FOR EPICORE)
  
 9) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS, AND LICENCE NUMBER ON EACH SHEET THAT BEARS
 THEIR SEAL PER
 61G15-23.002(2) FAC GUARD RAIL DETAIL IS MISSING
 ENGINEERS NAME AND PE LICENCE NUMBER
  
 10) FIRE SPRINKLERAND EPICORE FRAMING LAYOUT PLANS DO
 NOT CARRY AN ORIGINAL "SIGNATURE" AS REQUIRED BY
 61G15-23.002(2) FAC AND THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS
  
 11) THE ENGINEER SEAL ON THE TRUSS LAYOUT PLANS AND
 INDEX SHEETS DOES NOT MEET THE REQUIREMENTS OF
 61G15-23.001 FAC, 471.025 FS AND THE FBPE THAT THE
 WORDING ON THE SEAL SHALL CHANGE FROM CERTIFICATE TO
 LICENCE
  
 12) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC* PLEASE SEE THAT THE VALUE HAS BEEN
 INCREASED AND FEES ARE DUE
  
 13) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 14) NOTE: AN ELEVATION CERTIFICATE WILL BE REQUIRED
 PRIOR TO THE ISSUANCE OF A CO
  
 BLDG PLAN REVIEW