| Notes |
| Date |
Text |
| 2006-02-02 00:00:00 | DENIED:BUILDING B | | | 1.PERMIT APPLICATION INDICATES SHELL | | | ONLY. | | | | | | 2.THE MECHANICAL PLANS INDICATE | | | INSTALLATION OF THE CONDENSATE DRAIN | | | LINES. THE MECHANICAL NOTE #2, WASTE & | | | VENT PIPING SHALL BE PVC & DWV.FOR | | | FUTURE BUILDOUT - NO COMBUSTIBLES | | | ALLOWED IN THE RETURN AIR PLENUM PER | | | 2004 FMC 602.2.1. | | | | | | 3.PLAN SHEET M-1 & M-2, PLANS INDICATE | | | SLEEVES FOR FRESH AIR INTAKE & EXHAUST | | | AIR.PLEASE PROVIDE THE DISTANCE | | | BETWEEN THE TOP OF THE CONDENSING UNIT | | | TO THE FRESH AIR INTAKE.THE CONDENSING | | | UNIT WILL BE OMITTING HOT AIR WHICH | | | SHALL NOT BE RECIRCULATED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|