| 2005-12-23 00:00:00 | 1. BUILDING ADDRESS REQUIRED. A MINIMUM |
| | OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 2. BUILDING WILL BE REQUIRED TO BE FIRE |
| | SPRINKLER PROTECTED IN ACCORDANCE WITH |
| | FS 553.895 (2) |
| | |
| | 3. COULD NOT LOCATE ANY EXISTING OR NEW |
| | FIRE HYDRANTS. |
| | |
| | 4. A KNOX-BOX WILL BE REQUIRED FOR THE |
| | BUILDING. |
| | |
| | 5. NO FIRE SPRINKLER DRAWINGS PROVIDED |
| | WITH PLANS. |
| | |
| | 6. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER SYSTEM. |
| | |
| | 7. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM |
| | SHALL BE MONITORED BY A UL LISTED |
| | CENTRAL STATION APPROVED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 8. PLEASE PROVIDE PRESCRIPTVE STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. DETAILS LOCATED ON PAGE A-6. |
| | |
| | 9. MORE DETAILS REQUIRED ON AWNINGS. |
| | FLAME RETARDANCY WILL BE REQUIRED. |
| | |
| | 10. TENANT IMPROVEMENTS SHALL HAVE |
| | EMERGENCY LIGHTING AND ILLUMINATED EXIT |
| | SIGNS. |
| | |
| | 11. PLEASE ILLUSTRATE PORTABLE FIRE |
| | EXTINGUISHER LOCATIONS. |
| | |
| | 12. RENOVATION, CONSTRUCTION, AND |
| | DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | |
| | 13. SUITABLE ROADS ARE TO BE PROVIDED |
| | DURING CONSTRUCTION. |
| | |
| | 14. THE FIRE DEPARTMENT SPRINKLER |
| | CONNECTION SHALL BE LOCATED NO FARTHER |
| | THAN 150 FEET FROM A FIRE HYDRANT. |
| | |
| | 15. KNOX-BOX LOCKING CAPS SHALL BE |
| | PROVIDED ON THE FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |