| Plan Review Notes For Permit 05110800 |
| Permit Number |
05110800 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-11 15:24:32 | ************SHELL BUILDING ONLY************* | | | BUILDING A | | | | | | RESPONSE TO COMMENTS FROM REVIEW DATED 2-2-06: | | | | | | COMMENT 1:REPONSE INDICATES PER OUR CONVERSATION | | | METHOD A ENERGY CALCULATIONS WILL BE SUBMITTED WITH | | | SPEPARATE BUILD OUT PERMIT.PER 2004 FBC CHAPTER 13 | | | SUB-CHAPTER 13-101.1.1, NEW CONSTRUCTION COMEERCIAL | | | BUILDINGS SHALL COMPLY WITH SUBCHAPTER 13-4.METHOD B, | | | BUILDING, ENVELOPE TRADE-OFF METHOD IS REQUIRED FOR | | | SHELL BUILDINGS.THE METHOD A WILL BE REQUIRED FOR THE | | | BUILD-OUT PERMIT.THIS WAS ALSO A COMMENT BY THE | | | BUILDING PLANS EXAMINER. | | | | | | PLAN SHEET M-1A | | | SCOPE OF MECHANICAL WORK TO BE DONE UNDER THE SHELL | | | PERMIT IS AS FOLLOWS: | | | 1.DUCTLESS SPLIT UNIT TO THE ELEVATOR EQUIPMENT ROOM | | | 2.OUTDOOR INTAKES & EXHAUST LOUVERS, EXTENDING 12" | | | INTO BUILDING & CAPPED OF FUTURE. | | | | | | PLEASE NOTE, PVC REFRIGERANT RISER SHALL NOT BE A PASS | | | THROUGH ANY FUTURE PLENUMS. | | | | | | COMMENT 2 & 3 WERE ADDRESSED. | | | | | | ***NEW COMMENT**** | | | ADDITIONAL MECHANICAL PERMIT REQUIRED FOR THE BUILDOUT | | | PLAN SHEET M-1A INDICATES CONDENSING UNITS,PLEASE | | | NOTE CLEARANCES SHALL BE NO LESS THAN MANUFACTURER'S | | | RECOMMENDATIONS AND SUFFICIENT TO ALLOW INSPECTIONS, | | | SERVICE REPAIR OR REPLACEMENT PER 2004 FMC 306.1. |
|