| 2006-02-25 00:00:00 | PLUMBING PLAN REVIEW EXAMINER |
| | PAUL SCHMITZ 561-805-6692 |
| | [email protected] |
| | FBC PLUMBING 2004 |
| | FBC FUEL GAS 2004 |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | CH 1, ADMINISTRATION, 2004 EDITION ( |
| | ATFBC) FBC BUILDING 2004, CH 11 |
| | DENIED |
| | 1)PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT PLUMBING |
| | PLANS.ENGINEERING,MECHANICAL,ZONING, |
| | ELECTRICAL, BUIDING. |
| | 2) SHT M-2 REFERENCES BUILDING "B" |
| | PLEASE REFERENCEBUILDING "A" AS |
| | INDICATED ON PERMIT APPLICATION. |
| | 3)SHT M-3 RISER S-1, SEC 903.4 EVERY |
| | VENT STACK SHALL CONNECT TO THE BASE OF |
| | THE DRAINAGE STACK. |
| | 4)106.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | FOR BUILDINGS. THE EXAMINATION OF THE |
| | DOCUMENTS BY THE BUILDING OFFICIAL SHALL |
| | INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; |
| | FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN |
| | OR TRUSS LAYOUT; AND ALL EXTERIOR |
| | ELEVATIONS: |
| | PROVIDE SEPERATE SHEETS FOR PLUMBING |
| | AND,MECHANICAL. |
| | 5)WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | 6) PLEASE COMPLETELY REMOVE ANY |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |