Plan Review Notes For Permit 05110800
Permit Number 05110800
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-02 00:00:00DENIED:BUILDING B
 1.PERMIT APPLICATION INDICATES SHELL
 ONLY.
  
 2.THE MECHANICAL PLANS INDICATE
 INSTALLATION OF THE CONDENSATE DRAIN
 LINES. THE MECHANICAL NOTE #2, WASTE &
 VENT PIPING SHALL BE PVC & DWV.FOR
 FUTURE BUILDOUT - NO COMBUSTIBLES
 ALLOWED IN THE RETURN AIR PLENUM PER
 2004 FMC 602.2.1.
  
 3.PLAN SHEET M-1 & M-2, PLANS INDICATE
 SLEEVES FOR FRESH AIR INTAKE & EXHAUST
 AIR.PLEASE PROVIDE THE DISTANCE
 BETWEEN THE TOP OF THE CONDENSING UNIT
 TO THE FRESH AIR INTAKE.THE CONDENSING
 UNIT WILL BE OMITTING HOT AIR WHICH
 SHALL NOT BE RECIRCULATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.