| 2005-12-23 00:00:00 | 1. A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 2. THE BUILDING WILL BE REQUIRED TO BE |
| | FIRE SPRINKLER PROTECTED IN ACCORDANCE |
| | WITH FS 553.895 (2). |
| | |
| | 3. PLEASE ILLUSTRATE ALL PORTABLE FIRE |
| | EXTINGUISHER LOCATIONS. |
| | |
| | 4. COULD NOT LOCATE ANY NEW OR EXISTING |
| | FIRE HYDRANTS. |
| | |
| | 5. CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 6. SUITABLE ROADS ARE TO BE PROVIDED FOR |
| | FIRE AND PARAMEDICAL EQUIPMENT |
| | |
| | 7. SEPERATE PLANS PERMITS REQUIRED FOR |
| | FIRE SPRINKLER SYSTEM. |
| | |
| | 8. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM. NEW FIRE ALARM |
| | SYSTEM SHALL BE MONITORED BY A UL LISTED |
| | CENTRAL STATION APPROVED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 9. THE FIRE DEPARTMENT SPRINKLER |
| | CONENCTION SHALL BE LOCATED NO FARTHER |
| | THAN 150 FEET FROM A FIRE HYDRANT. |
| | |
| | 10. KNOX-BOX LOCKING CAPS WILL BE |
| | REQUIRED FOR THE FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | 11. EMERGENCY LIGHTS AND EXIT SIGNS WILL |
| | BE REQUIRED WITHIN THE TENANT SPACES. |
| | |
| | 12. BUILDING ADDRESS WILL BE REQUIRED. A |
| | MINIMUM OF AT LEAST 6" HIGH WILL BE |
| | REQUIRED. |
| | |
| | 13. MORE DETAILS REQUIRED ON AWNING. |
| | FLAME RETARDANCY WILL BE REQUIRED. |
| | |
| | 14. NO FIRE SPRINKLER PLANS PROVIDED |
| | WITH DRAWINGS. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |