| 2005-12-25 00:00:00 | IN ELEC FOR REVIEW. |
| | *** UNSAT *** |
| | |
| | 1)NOTE: PLEASE BE SURE PLANS, A-SHEETS |
| | ETC REFERENCE THE CURRENT CODES IN |
| | EFFECT AND APPLIED UNDER. |
| | (2004 FBC , 2002 NFPA-72, 2003 NFPA-101, |
| | 2002 NFPA-70 |
| | |
| | 2)NOTE: PLEASE SSE FIRE REVIEW COMMENTS |
| | WHICH WILL HAVE A DIRECT AFFETC ON |
| | ELECTRICAL PLANS. |
| | |
| | 3)NOTE: PLEASE SEE NFPA-101 7.8 , 7.9 |
| | WHICH REQUIRES STAIRWAYS TO HAVE A MIN |
| | OF 10FT CANDLES DURING NORMAL POWER AND |
| | 1FT CANDLE UNDER EM POWER/BATTERY BACK |
| | UP. |
| | PLEASE PROVIDE PHOTOMETRICS FOR THIS. |
| | MAY BE A BRIEF DETAIL FOR THE MIN NEEDED |
| | TO PUBLIC RIGHT OF WAY. |
| | |
| | 4)NOTE: PLEASE SEE 250.50 WHICH ALSO |
| | REQUIRES THE FOOTER STEEL TO BE PART OF |
| | THE GROUNDING ELECTRODE SYSTEM. PLEASE |
| | ADD. |
| | PLEASE INCLUDE. |
| | |
| | 5)NOTE: PLEASE CORRLELATE RISER WITH |
| | HOUSE PANEL. PLEASE SEE RISER INDICATES |
| | PANEL "H" AS 225A MCB , HOWEVER PANEL |
| | INDICATES BEING MLO? |
| | |
| | 6)NOTE: PLEASE VERIFY CIRCUTIING FOR |
| | FOUNTAIN PUMP MOTOR, FOUNTAIN LTS, AND |
| | HOUSE LTS. PLEASE SEE SHEET E-4 SHOWS |
| | ALL THESE ON THE SAME CIRCUIT, HOWEVER |
| | PANEL SCHEDULES DOES NOT SHOW THIS. |
| | PLEASE LIST THE FOUNTAIN LTS. |
| | PLEASE ALSO SEE WHAT APPEARS TO BE |
| | CANOPY LTS WHICH ARE ALSO ON SAME?? |
| | 430.148 ETC. |
| | PLEASE SEE LOAD IS SHOWN AT 900VA, |
| | HOWEVER WITH ALL OF THESE ON THIS |
| | CIRCUIT, THE VA IS HIGHER. |
| | PLEASE ALSO VERIFY AS SUBMERSIBLE 120 |
| | LTS WOULD BE GFI PROTECTED. |
| | 680. |
| | |
| | 7)NOTE: PLEASE CLARIFY THE EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO HOSE |
| | PANEL. |
| | 250.110,250.24, 250.122 |
| | |
| | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVEIW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |