| 2006-03-02 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) SUBMIT PRODUCT APPROVALS, |
| | THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | |
| | 2) SUBMIT SITE PLAN, |
| | DRAWINGS SHALL SHOW THE LOCATION OF ALL |
| | WORK, INCLUDING THE PROPOSED BUILDING(S) |
| | OR STRUCTURE(S), AND ALL EXISTING |
| | MAN-MADE IMPROVEMENTS AND EVERY EXISTING |
| | SURVEY, OR OTHER SPECIAL SURVEY, |
| | PREPARED BY A QUALIFIED SURVEYOR. PER |
| | 106.3.4 FBC* |
| | |
| | 3) SUBMIT SOIL REPORT PER 1802.2.1 FBC |
| | AND 106.3.5.1.1 FBC* |
| | |
| | 4) DRAWINGS SHALL SPECIFY CONSTRUCTION |
| | TYPE WITH AREA AND HEIGHT MODIFICATIONS |
| | USED TO MEET CODE |
| | |
| | 5) AN AUTOMATIC FIRE SPRINKLER SYSTEM |
| | SHALL BE INSTALLED PER 903.2.10 FBC, |
| | PROVIDE DRAWINGS |
| | |
| | 6) PROVIDE ENERGY CALCULATIONS AND |
| | COMPLIANCE WITH 13-101.1.6 AND |
| | 13-103.1.1.1 FBC |
| | |
| | 7) SUBMIT ENGINEERED TRUSS DRAWINGS PER |
| | 2303.4.1 AND ENGINEERING NOTE 1 OF TRUSS |
| | DESIGN CRITERIA ON S/4 |
| | |
| | 8) S/4 HAS REFERENCE TO STANDING SEAM |
| | METAL ROOF AND A/3 HAS CONCRETE ROOF |
| | TILE, CLARIFY |
| | |
| | 9) GUARDS ON A/3 AND A/5 DO NOT MATCH |
| | |
| | 10) SIGN AND AWNINGS SHALL BE SUBMITTED |
| | UNDER SEPERATE PERMITS |
| | |
| | 11) DRAWINGS MISSING SITE,PARKING,ETC, |
| | TO REVIEW FOR ACCESSABILITY, COMPLY WITH |
| | REQUIREMENTS OF CHAPTER 11 FBC |
| | |
| | 12) DRAWINGS MISSING REQUIRED FOR REVIEW |
| | OF EGRESS, COMPLY WITH REQUIREMENTS OF |
| | CHAPTER 10 FBC |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT SET |
| | OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 14) PROVIDE STAIR SHOP DRAWINGS FOR |
| | COMPLIANCE, ATTACHMENT, ETC. |
| | |
| | 15) PROVIDE COMPLIANCE OF GUARDS WITH |
| | 1607.7 FBC |
| | |
| | 16) UPON SUBMITTAL OF THESE REQUIREMENTS |
| | FURTHER COMMENTS MAY BE GENERATED |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |