| Date |
Text |
| 2006-06-07 00:00:00 | *********** UNSAT 5TH TIME. ********** |
| | |
| | PLEASE SEE NOTES FROM PREVIOUS REVIEWS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1 |
| | UNDER THE 2004 FBC. |
| | PLEASE KNOW IT WAS DISCUSSED WITH THE |
| | ARCHITECT THAT ONE OF TWO SCENERIO'S FOR |
| | THIS COMPLIANCE NEEDED TO TAKE PLACE ON |
| | THE PLANS. EITHER MEET THE EXCEPTION AS |
| | SETFORTH FOR TENANT SPACE IN BUILDING |
| | WITH PERCENTAGE OR PROVIDE A LIGHTING |
| | CONTROL SYSTEM OF SOME SORT TO SHUT |
| | LIGHTING DOWN AS REQUIRED. |
| | NEITHER ITEMS WERE SHOWN, OR NOTED ON |
| | PLANS?? |
| | ** PLEASE SEE NEW PANEL SPECS FOR EACH |
| | OF THE TWO EXISTING PANELS WERE ADDED TO |
| | PLANS WHICH WAS NOT PART OF ANY OF THE |
| | PREVIOUS COMMENTS AND IT IS UNCLEAR WHY |
| | THESE WERE ADDED.? |
| | |
| | 2)NOTE: PLEASE SEE LOAD SUMMARYS ON E-1 |
| | AND E-2 STILL DO NOT CORRELATE??? |
| | 65.1,72.7?? WHICH IS IT? IF GOING BY THE |
| | LOAD CALCULATIONS AS SHOWN ON PANELS |
| | WHICH NOW SEEM TO BE CORRECT. |
| | |
| | |
| | CALLED CONTRACTOR WITH THE ASST BUILDING |
| | OFFICIAL MR ROBERT BROWN AFTER GOING |
| | OVER COMMENTS AND PLANS. LEFT MESSAGE |
| | FOR MR. DAVE DAVORE. |
| | |
| | PLANS WILL BE ROUTED TO MR LUIS |
| | MARTINEZ. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION AS |
| | REQUESTED. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |