Plan Review Notes
Plan Review Notes For Permit 05110790
Permit Number 05110790
Review Stop E
Sequence Number 5
Notes
Date Text
2006-06-07 00:00:00*********** UNSAT 5TH TIME. **********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS.
  
  
 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1
 UNDER THE 2004 FBC.
 PLEASE KNOW IT WAS DISCUSSED WITH THE
 ARCHITECT THAT ONE OF TWO SCENERIO'S FOR
 THIS COMPLIANCE NEEDED TO TAKE PLACE ON
 THE PLANS. EITHER MEET THE EXCEPTION AS
 SETFORTH FOR TENANT SPACE IN BUILDING
 WITH PERCENTAGE OR PROVIDE A LIGHTING
 CONTROL SYSTEM OF SOME SORT TO SHUT
 LIGHTING DOWN AS REQUIRED.
 NEITHER ITEMS WERE SHOWN, OR NOTED ON
 PLANS??
 ** PLEASE SEE NEW PANEL SPECS FOR EACH
 OF THE TWO EXISTING PANELS WERE ADDED TO
 PLANS WHICH WAS NOT PART OF ANY OF THE
 PREVIOUS COMMENTS AND IT IS UNCLEAR WHY
 THESE WERE ADDED.?
  
 2)NOTE: PLEASE SEE LOAD SUMMARYS ON E-1
 AND E-2 STILL DO NOT CORRELATE???
 65.1,72.7?? WHICH IS IT? IF GOING BY THE
 LOAD CALCULATIONS AS SHOWN ON PANELS
 WHICH NOW SEEM TO BE CORRECT.
  
  
 CALLED CONTRACTOR WITH THE ASST BUILDING
 OFFICIAL MR ROBERT BROWN AFTER GOING
 OVER COMMENTS AND PLANS. LEFT MESSAGE
 FOR MR. DAVE DAVORE.
  
 PLANS WILL BE ROUTED TO MR LUIS
 MARTINEZ.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AS
 REQUESTED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]