Plan Review Notes
Plan Review Notes For Permit 05110790
Permit Number 05110790
Review Stop M
Sequence Number 4
Notes
Date Text
2006-06-13 00:00:00PROVISO:
  
 1.ROOF CURBS SHALL EXTEND A MINIMUM OF
 8" ABOVE THE ROOF SURFACE IN ACCORDANCE
 WITH 2004 FBC 1509.7.
  
 2.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION, & HOOD.PLEASE
 PROVIDE THE MANUFACTURE SUBMITTAL DATA
 FOR THE WALK-IN COOLER WITH PERMIT
 APPLICATION.HOOD & FIRE SUPPRESSION
 PLANS SUBMTITED WITH BUILDING PLANS.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 2004 FMC 606.2.1 WITH
 NOTIFICATION AS SPECIFIED IN 2004 FMC
 606.4 & 606.4.1.
  