| 2006-05-14 00:00:00 | PLANS SUBMITTED BY E-MAIL. |
| | REVIEW DONE AS PER ROBERT BROWN AND LUIS |
| | MARTINEZ. |
| | |
| | PLEASE SEE COMMENTS BELOW WHICH WERE |
| | E-MAILED BACK TO BOTH ARCHITECTS. |
| | |
| | 1) NOTE: PLEASE SEE "WINDOW " RECEPT BY |
| | FRONT DOOR IS STILL ON B-23 WITH OTHER |
| | DINING AREA RECEPTS. |
| | 2)NOTE: PLEASE SEE LIGHTING CONTROL IN |
| | REQUIRED AS THE "BUILDING" IS OVER 5000 |
| | SQ FT. PLEASE SEE FBC AS THIS OCCUPANCY |
| | IS IN THE REST OF THE LARGERBUILDING. |
| | 3) NOTE: PLEASE SEE LOADS FOR A/C UNITS |
| | STILL DO NOT CORRELATE IN PANEL SCHEDULE |
| | WHICH IN TURN REFLECTS ALL LOADS. |
| | PLEASE GO VER ALL LOAD CALCULATIONS. |
| | 4) NOTE: PLEASE SEE LOADS IN SUMMARY DO |
| | NOT CORRELATE WITH LOADS ON RISER SHEET. |
| | PLEASE SEE NOW, THE MIN AIC RATINGS FOR |
| | PANELS A AND B HAVE BEEN REMOVED.? |
| | PLEASE KNOW, I WILL BE OUT OF THE OFFICE |
| | BY THIS THURS THE 18TH. |
| | 5) NOTE: PLEASE KNOW, THE CHIEF |
| | ELECTRICAL INSPECTOR HAS VERIFIED THE |
| | NUMBER OF SERVICE MAINS AT TENANT |
| | LOCATION AND THIS NEW MAIN SHOULD BE OK. |
| | PLEASE PROVIDE BOLLARDS AS SHOWN FOR |
| | PROTECTION OF NEW SERVICE MAIN BEING |
| | ADDED TO THE END OF BUILDING. |
| | THESE REVISIONS, NEED TO GO THOUGH THE |
| | ENGINEER TO BE VERIFIED. |