| 2006-05-09 00:00:00 | PROVISO: |
| | |
| | FIRE DAMPERS REQUIRED WHERE DUCTS |
| | PENETRATE WALL BETWEEN THE KITCHEN AND |
| | THE CORRIDOR.PLAN SHEET A.1 INDICATES |
| | THIS AS A 1 HR CORRIDOR.PLANS DO NOT |
| | INDICATE RATING OF THE WALL BETWEEN THE |
| | CORRIDOR AND THE RESTROOMS. THE "1 HR |
| | CORRIDOR" WOULD INDICATE ALL WALLS |
| | ENCLOSING THE CORRIDOR WILL BE RATED IN |
| | WHICH THE PENETRATIONS FROM THE CORRIDOR |
| | INTO THE RESTROOMS WOULD ALSO REQUIRE |
| | FIRE DAMPERS.PLEASE REVISE |
| | ARCHITECTURAL PLANS SHOULD THE PARTITION |
| | BETWEEN THE CORRIDOR AND THE RESTROOMS |
| | IS NOT IN FACT A "1 HR" PARTITION. |
| | |
| | PLEASE NOTE, PLAN SHEET M.1 FIRE DAMPER |
| | DETAIL STATES FIRE DAMPER PENETRATION TO |
| | HAVE 3M FIRE STOP.PLEASE CHECK FIRE |
| | DAMPER INSTALLATION INSTRUCTIONS FOR |
| | APPROVAL OF THIS APPLICATION.FIRE |
| | DAMPERS ARE MADE TO EXPAND AND WILL NOT |
| | FUCTION PROPERLY WITH FIRE STOP. |
| | PROVIDE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS FOR THE FIRE DAMPERS ON THE |
| | JOBSITE FOR INSPECTION. |
| | |
| | HOOD AND FIRE SUPPRESSION PLANS |
| | SUBMITTED AND APPROVED WITH BUILDING |
| | PLANS.ADDITIONAL PERMIT REQUIRED FOR |
| | HOOD, FIRE SUPPRESSION, AND WALK-IN |
| | COOLERS. |
| | |