Text |
| 2006-05-31 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE BE AWARE THAT DOOR SCHEDULE | | | NOTE ON A.3 STILL REFERENCES THE | | | INCORRECT LIFE SAFETY CODE. NFPA 101, | | | 2003 EDITION SHALL BE REFERENCED. PLEASE | | | REFER TO LAST FIRE REVIEW. | | | | | | 2) EXTERIOR DOORS SHALL NOT BE EQUIPED | | | WITH KEY LOCKS UNLESS THE CRITERIA OF | | | NFPA 101, SECTION 7.2.1.5.3 IS MET. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|