Plan Review Notes
Plan Review Notes For Permit 05110790
Permit Number 05110790
Review Stop E
Sequence Number 3
Notes
Date Text
2006-05-08 00:00:00***********UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE PLANS CONTAIN NOTES FROM
 PREVIOUS REVIEWS WHICH STILL NEED TO BE
 ADDRESSED ALONG WITH NEW COMMENTS AS
 PLANS HAVE HAD CHANGES ONCE AGAIN.
  
 ** PLEASE ALSO SEE PLANS ARE CONTAIN
 REVISIONS TO MECHANICAL AND BUILDING
 WHICH WILL REQUIRE NEW REVIEWS OF THOSE
 SAID PLANS.
  
 ** PLEASE SEE NOTES BELOW AS NOTES ARE
 TAKEN DIRECTLY FROM PREVIOUS REVIEW.
 PLEASE SEE NEW NOTES AT THE BOTTTOM OF
 REVIEW.
  
 ******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL NEEDING TO BE ADDRESSED
 AND NEW COMMENTS TO CHNAGES IN PLANS
 FROM PREVIOUS PLANS SUBMITTED.
  
 * PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE END OF FIRST
 REVIEW NOTES.
  
 ************ UNSAT ************
  
  
 1)NOTE: NOTE #1, NO.SEE NOTES WITH
 RESPECT TO THE FBC CHAPTER 13.
  
 ** PREVIOUS REVIEW **
 NOTE #1 NO, PLEASE SEE PREVIOUS
 NOTE AS PLANS ORIGINALLY CAME IN
 DESIGNED UNDER THE 2001 FBC WHEN THE
 CODE IN EFFECT AT THAT TIME WAS THE
 2004. PLEASE SEE PREVIOUS NOTE MENTIONED
 TO PLEASE MAKE ALL CHANGES IN DESIGN TO
 THE 2004 FBC.
 PLEASE SEE NEW NOTES BELOW.
  
 ** PRE-REVIEW**
 PLEASE SEE PLANS STATE THE 2001
 FBC, HOWEVER AS OF OCT. 1ST, 2005 THE
 CODE HAS CHANGED TO THE 2004 FBC AND ALL
 OTHER RELEVANT CODES.
 PLEASE SEE PERMIT WAS NOT APPLIED FOR
 UNTIL NOV. 21ST, 2005
 PLEASE ADJUST ALL PLANS.
  
 2)NOTE: NOTE #2 OK.
  
 ** PRE-REVIEW**
  
 PLEASE SEE ALL SHEETS IN BOTH SETS ARE
 SEALED PHOTOCOPIES OF SIGNED PLANS.
 PLEASE SEE FS 481.221 AND FAC
 61G1-16.003 WHICH REQUIRE THE PLANS TO
 HAVE AN "ORIGINAL WET SIGNATURE AND
 DATE".
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 ONE SET MAY BE RETAINED.
  
 3)NOTE: NOTE #3 OK.
  
 ** PREVIOUS NOTE **
 NOTE #3 OK, HOWEVER SEE NEW
 NOTES FOR HAND DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW**
 PLEASE SEE ELECTRICAL SHEETS
 CONTAIN A TITLE BLOCK FOR AN ENGINEER.
 PLEASE KNOW, IF THIS ENGINEER IS
 RESPONSIBLE FOR DESIGN OR ELECTRICAL
 WORK ON SAID PLANS, THEN PLANS MUST BE
 SIGNED DATED AND SEALED BY SAID
 ENGINEER.
 FS 471.025
 PLEASE ALSO SEE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002 WHICH REQUIRES THE
 TITLE BLOCK FOR ENGINEER TO BE COMPLETE
 WITH ALL INFORMATION AS SET-FORTH IN THE
 LISTED FAC.
  
 4)NOTE:NOTE #4 OK.
  
 ** PRE-REVIEW**
 PLEASE SEE 600.5 FOR MISSING
 REQUIRED SIGN CIRCUIT.
  
 5)NOTE:NOTE #5 NO, PLEASE SEE A
 CIRCUIT AND LOAD IS BEING ADDED TO PANEL
 "B" CIRCUIT #10. PLEASE SEE RECEPT IS
 STILL NOT BEING SHOWN ABOVE THE WINDOW
 AND HOW LOADS WERE DERIVED FOR THIS CAN
 NOT BE VERIFIED AS NOW ONLY A LOAD OF
 1.6KW IS SHOWN. IS THIS AT 200VA PER FT?
 THIS IS NOT SHOWN IN CALCUALTIONS.
 AS STATED IN BOTH PREVIOUS REVIEWS,
 PLEASE SEE 210.62,220.12A.
  
  
 ** PREVIOUS NOTE**NOTE #5 OK, HOWEVER
 PLEASE SEE THESE ARE NOW ADDED, BUT TO
 THE GENERAL
 RECEPTS IN DINING AREA. PLEASE KNOW,
 THESE SHOULD BE DEDICATED PER LOADS.
 PLEASE SEE210.62,220.12A,220.3(B)(7)
 CODE COMMENTARY FOLLOWING IN THE 2002
 NEC HANDBOOK.
  
 ** PRE-REVIEW**
 PLEASE SEE MISSING REQUIRED
 WINDOW OUTLETS ABOVESTORE FRONT.
 210.62.
 PLEASE SEE MIN KVA TO BE FIGURED PER
 220.12A
 THIS IS TO DISCOURAGE FLOOR RECEPTACLES
 AND UNSIGHTLY EXTENSION CORDS USED FOR
 SIGNAGE, DIPLAYS ETC WHICH ARE LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE THE WINDOW.
  
 6)NOTE:NOTE #6 OK, NOW SHOWN CIRCUITED
 TO LOCAL LIGHTING.
  
 ** PREVIOUS NOTE **
 NOTE #6 NO, PLEASE SEE THESE ARE
 STILLNOT SHOWN CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT AS REQUIRED PER 700.12E.
 PLEASE SEE CIRCUITING AS SHOWN AND
 "LOCK-OFF" DEVICE LISTED ON PANEL
 SCHEDULE DOES NOT MEET THE "EXCEPTION"
 AS NOTED.
  
 ** PRE-REVIEW**
 PLEASE SEE 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING SHOWN ON PLANS.
  
 7)NOTE: NOTE #7 OK.
  
 ** PRE-REVIEW**
 PLEASE COMPLETE SWITCH
 LEGS.SWITCH BANK ON PLANS.
 CAN NOT VERIFY AT THIS TIME.
  
 8)NOTE: NOTE #8 OK.
  
 ** PREVIOUS NOTE **
 NOTE #8 OK, HOWEVER SEE NEW
 NOTE FOR HAND-DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW **
 PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: NOTE #9 NO, NEW LOADS SUBMITTED
 HOWEVER PLEASE SEE COMMENTS AS LOADS
 FROM E-1 AND E-2 DO NOT CORRELATE.
 PLEASE CLARIFY WHAT IS NOW BEING SHOWN
 AS 85% POWER FACTOR? WHAT IS THIS?
 PLEASE SEE AS STATED ON PREVIOUS
 REVIEWS, SUBMIT EITHER COMPLETE LOAD
 CALCULATIONS, OR A 12 MONTH READING FROM
 FPL,WITH NEW LOADS ADDED AT 125%.
 PLEASE SEE NEC 220.35
  
 ** PREVIOUS NOTE **
 NOTE # 9 NO. NONE SUBMITTED.
 PLEASE SEE NEW SERVICE AS SHOWN COMES
 FROM AN EXISTING SERVICE ON MAIN
 BUILDING AND ADDED LOAD TO THE EXISTING
 SERVICE MUST BE VERIFIED.
 PLEASE SEE NEW COMMENTS FOR MANY CHANGES
 ON RISER.
  
 ** PRE-REVIEW**
 PLEASE PROVIDE COMPLETE LOAD
 CALCULATION ON EXISTING SERVICE WHICH
 THIS SERVICE IS BEING TIED INTO.
 IT IS KNOWN TO THIS OFFICE THAT THE
 SERVICE AT THIS LOCATION CONTAINS LOADS
 ON SOME OF THE MAIN SERVICES WHICH ARE
 CLOSE TO EXCEEDING RATED LOADS.
 215.5,220
  
 10)NOTE: NOTE #10, OK, HOWEVER PLEAS
 KNOW, THE AVAILABLE FAULT CURRENT IS
 STILL SHOWN AS 37,880 AND AIC RATINGS
 FOR MAINS AND BRANCH BRKRS ARE BEING
 SHOWN AT 100,000. PLEASE KNOW, THIS IS
 PERMITTED AND COMMENT HAS BEEN
 ADDRESSED. IT IS BEING NOTED AS THE 100K
 RATTING SEEMS VERY HIGH. IF SHOWN ON
 PLANS, THEN THIS IS WHAT WILL BE
 REQUIRED TO BE INSTALLED.
  
 ** PREVIOUS NOTE **
 NOTE #10 NO?? PLEASE SEE A NOTE
 WAS ADDED FOR "DOWN SYSTEM BREAKER
 SERIES". THIS IS UNCLEAR AS AN AVAILABLE
 FAULT CURRENT IS NOTED AS 37,880 FROM
 FPL, YET THE SERIES RATINGS ARE NOW
 SHOWING 100K??
 PLEASE KNOW, AIC RATINGS SHALL BE STATED
 FOR NEW MAINS, NEW PANELS AND SERIES
 RATING ON BRANCH BRKRS.
 110.9,215.5
  
 ** PRE-REVIEW **PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALL-ED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
 PER 110.9/215.5
  
 11)NOTE: NOTE #11 OK, PLEASE SEE NO MAIN
 IS BEING SHOWN ON THE LINE SIDE OF
 SERVICE MAINS.
 PLEASE SEE NEW COMMENT FOR THE NUMBER OF
 MAINS.
  
 ** PREVIOUS NOTE **NOTE: 11 NO, PLEASE
 SEE THE
 "EQUIPMENT GROUNDING CONDUCTOR" IS NOW
 REMOVED, HOWEVER MAY BE REQUIRED AS THE
 "SERVICE MAIN" IS STILL NOT SHOWN OR
 INDICATED ON PLANS.
 PLEASE KNOW, IF THE "SERVICE MAIN" FOR
 BUILDING IS LOCATED AHEAD OF GUTTER
 SHOWN, THE NEUTRAL AND EQUIPMENT
 GROUNDING CONDUCTORS SHALL NOT BE BONDED
 AFTER THE FIRST MEANS OF DICSCONNECT.A
 "FLOATING NEUTRAL" WILL BE REQUIRED.
  
 ** PRE-REVIEW**
 PLEASE SEE 250.6 , 250.24, IT
 IS NOT SHOWN IF THERE IS A "MAIN" ON THE
 LINE SIDE OF THE GUTTER SHOWN.
 THEREFORE, THE 'EQUIPMENT GROUND" SHOWN
 FROM GUTTER TO METER AND METER TO MAIN
 SHOWN, MAY BE PARALLING THE NEUTRAL.??
 CAN NOT VERIFY AT THIS TIME?
  
 12)NOTE: NOTE #12, OK. SEE NEW NOTES FOR
 OTHER CHANGES.
  
 ** PREVIOUS NOTE **
 NOTE#12 NO, PLEASE SEE NEW
 COMMENTS AS RISER DIAGRAM HAS COMPLETELY
 CHANGED FROM PREVIOUS PLANS AND MANY
 CHANGES TO SERVICE WERE MADE.
  
 **PRE-REVIEW**
 PLEASE CORRELATE RISER WITH
 PANELS. PLEASE SEE PANEL "B" IS SHOWN AS
 MLO ON SCHEDULE, HOWEVER RISER SHOWS
 MCB.
  
 13)NOTE:NOTE #13 OK.
  
 **PRE-REVIEW**
 PLEASE SEE CONTINUOUS LOADS ARE
 SHOWN AT 125%, HOWEVER PLEASE ALSO
 INDICATE ANY LARGEST MOTORS LOADS ALSO
 @125%.
 215.3, 230.42 ETC.
  
 14)NOTE: NOTE #14 OK.
  
 ** PRE-REVIEW** PLEASE PROVIDE DETAIL
 FOR MEANS
 OF SHUT DOWN OF ALL ELECTRICAL FOR HOOD.
 NFPA-96
  
  
 ***************************************
 ******* NEW COMMENTS "2ND REVIEW"******
  
 15) NOTE: NOTE: OK.
  
 ** PREVIOUS NOTE **
 PLEASE KNOW, THESE PLANS ARE
 SIGNED DATED AND SEALED PLANS BY AN
 ENGINEER UNDER FLORIDA STATUES 471.
 PLEASE KNOW, HAND DRAWN CHANGES TO
 PLANS, FOR CIRCUITING, DESIGN, NOTES ETC
 ARE NOT PERMITTED UNDER FS 471.
 PLEASE KNOW, AN ENGINEER MAY MAKE
 CHANGES TO SAID PLANS, HOWEVER EACH AND
 EVERY ITEM IS REQUIRED TO BE SIGNED AND
 DATED AND "WHITE-OUT" ON PLANS IS NOT
 PERMITTED.
 PLEASE SEE PLANS CONATIN MANY AREAS
 WHERE CHANGES WERE MADE , SOME AREAS
 WHERE "WHITE-OUT WAS USED AND AREA WHERE
 CORRECTIONS WERE "PASTED" OVER PLANS.
 PLANS SHALL BE RE-PRINTED WITH ALL
 CORRECTIONS, SIGNED, DATED AND SEALED BY
 SAID ENGINEER OF RECORD.
 PLEASE SEE COMMENT BELOW AS COPIES OF
 PLANS ARE BEING RETAINED.
  
 16)NOTE: NOTE #16 NO, PLEASE SEE MANY
 LOADS DO NOT MATCH.
 PLEASE SEE LOADS HAVE DECREASED ON PANEL
  
 SCHEDULES ON CALCS AT THE BOTTOM OF THE
 PANEL SCHEDULES, HOWEVER THE LOADS WERE
 INCREASED. PLEASE SEE ALL LOADS ON
 PANELS "A" AND "B". PLEASE SEE PANEL "A"
 WHICH WENT FROM 41.5KVA WHICH INDICATED
 120A'S TO 38.8 KVA AND IS NOW 132A'S??
 THE LOAD DECREASED DUE TO CHANGES,
 HOWEVER LOAD AT PANEL INCREASED??
 PLEASE SEE IN EITHER CASE THE FINAL
 AMPERAGE FROM THE KVA'S SHOWN ARE NOT
 ACCUARATE.
 PLEASE SEE "C" PHASE LOAD INCREASED, YET
 NO LOADS ON PANEL SCHEDULE INCREASED??
  
 PLEASE ALSO SEE THE SAME FOR PANEL "B",
 WHICH SHOWS A SMALL INCREASE DUE TO THE
 ADDITION OF THE SHOW WINDOW KVA, HOWEVER
 PLEASE SEE LOAD CALCULATIONS STILL DO
 NOT CORRELATE. PLEASE SEE KVA IS SHOWN
 @33.9KVA WHICH AT 120/208 3-PHASE IS NOT
 102A'S.
 PLEASE SEE E-2 NOW MENTIONS FOR SERVICE
 TO BE A 250A, YET RISER SHOWS 225A?
 PLEASE SEE LOAD ON E-1 IS NOW THE SAME
 AS THE LOAD ON E-2 FOR SERVICE.
 PLEASE CLARIFY WHERE THESE EXTRA LOADS
 ARE COMING FROM?
 PLEASE SEE NEW NOTES FOR A/C LOADS WHICH
 HAVE COMPLETELY CHANGED.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE ALL PANELS ON
 RISER, PANEL SCHEDULES AND SEE NOTES AS
 CODE VIOLATIONS ARE SHOWN FOR NEW
 REVISIONS.
 A)PLEASE SEE RISER NOW SHOWS PANELS AS
 200A BEING FED FROM A 400A DISCONNECT
 AND 400A OCP.?? ORIG RISER SHOWED 400A
 PANELS.
 B)PLEASE SEE BOTH PANELS ARE NOW LISTED
 AS 200A ON RISER AND 225A ON PANEL
 SCHEDULES.??? ORIG PLANS INDICATED
 PANELS ON SCHEDULES AS 400A, ONLY PANEL
 "B" WAS SHOWN AS 400A MCB ON RISER, YET
 400A MLO ON SCHEDULE.
 PLEASE SEE FEEDER TO PANEL "A" STILL
 SHOWN AS 500 MCM'S WHICH ARE RATED AT
 400A'S>
 C) PLEASE SEE LOAD CALCULATIONS MENTIONS
 300A SERVICE.? PLEASE CORRELATE.
 215.5, 2002 NEC.
  
 17) NOTE: NOTE#17 NO? PLEASE SEE NOTHING
 WAS SUBMITTED FOR ANY LIGHTING CONTROLS.
 PLEASE SEE NO RESPONSE WAS NOTED FROM
 DESIGNER TO INDICATE COMPLIANCE FOR
 LIGHTING CONTROLS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE PREVIOUS REVIEW
 REQUESTED DESIGN TO MEET 2004 FBC AS
 PLANS WERE SUBMITTED AFTER 1ST OCT, 2005
 WHEN THE CODE CHANGED.
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1FOR NEW LIGHTING
 CONTROLS REQUIRED. PLEASE SUBMIT A
 METHOD, AND TIME OF DAY SCHEDULING.
 PLEASE ALSO SEE 13-415.1.ABC.1.2
  
 18) NOTE: NOTE #18 NO, PLEASE SEE A
 NOTICE WAS GIVEN TO BE SURE "ALL"
 COMMENTS FOR CODE COMPLIANCE WAS
 ADDRESSED. PLEASE KNOW THE ENGINEER OF
 RECORD TO DATE HAS NOT CONTACTED THIS
 OFFICE WITH ANY QUESTIONS, OR COMMENTS.
 PLEASE KNOW, THE CONTACT WHICH WERE MADE
 WERE DONE BY THE ARCHITECT OF RECORD.
 PLEASE SEE A FEE HAS NOW BEEN ASSESSED.
 THIS IS THE SOLE RESPONSIBILITY OF THE
 DEISGNER OF RECORD AND IS NOT ASSESSED
 TO THE OWNER OR CONTRACTOR.
 PLEASE SEE THE AMOUNT OF $2,520 HAS BEEN
 ATTACHED AND IS REQUIRED TO BE PAID
 BEFORE RESUBMITTING PLANS.
 PLEASE KNOW, IT IT STRONGLY RECOMMENDED
 A MEETING BE HELD WITH PARTIES OF
 RESPONSIBILITY TO THIS PROJECT TO HELP
 ALLEAVIATE ANY FURTHER DELAYS IN
 ISSUANCE OF THIS PROJECT.
  
  
 ** PLEASE KNOW, ONE SET OFELECTRICAL
 PLANS HAVE BEEN RETAINED FOR FILE.
 PLEASE KNOW, PLANS WILL ALSO BE FORWARD
 TO THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS FOR REVIEW.
  
 ** PREVIOUS NOTE **
 PLEASE SEE COPY OF FLORIDA
 STATUES 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS
 FOR CODE COMPLIANCE. PLEASE KNOW, IF ANY
 OF THE SAME COMMENTS FROM THE FIRST TWO
 REVIEWS ARE NOT ADDRESSED FOR THIRD SUCH
 REVIEW, THIS OFFICE WILL HAVE NO CHOICE
 BUT TO ASSESS A 4X FEE FOR THE PLAN
 REVIEW PORTION OF THE PERMIT FEE. (30%
 OF BASE FEE X4).
 PLEASE KNOW, TO DATE THIS OFFICE HAS NOT
 BEEN CONTACTED FOR ANY QUESTIONS OR
 COMMENTS.
  
  
 ************ NEW NOTES 3RD REVIEW *****
 DUE TO CHANGES IN PLANS , PLEASE SEE
 NOTES BELOW.
  
 1) NOTE: PLEASE SEE MECHANICAL LOADS
 HAVE BEEN NOTED AS BEING 7.8 KW,
 ALTHOUGH LOADS ON THE PANEL SCHEDULE
 ITSELF REMAIN THE SAME AS THE PERVISOU
 TWO SETS??
 PLEASE SEE THE LOADS AHVE NOW DECREASED,
 YET THE OCP FOR ONE HAS INCREASED AND
 THE OTHER HAS REMAINED THE SAME AS
 BEFORE.
 PLEASE SEE THIS DOES NOT CORRELATE WITH
 MECHANICAL PLANS,AS THE MECHANICAL PLANS
 NOW INDICATE THE KW RATINGS LESS THAN
 HALF OF THE PREVIOUS PLANS.
 PLEASE SEE MECHANICAL PLANS, AS THE OCP
 IS MUCH LOWER THAN THE MAX OCP ON THE
 ELECTRICAL PLANS.
 PLEASE CORRELATE, PLEASE ADJUST LOADS,
 PLEASE ADJUST OCP.
 215.5.
  
 2) NOTE: PLEASE SEE AN ELECTRICAL
 SERVICE ELEVATION IS NOW BEING SHOWN.
 PLEASE VERIFY NO MORE THAN 6 MEANS OF
 DISCONNECT FOR SERVICE.
 230.70,230.71,230.72
 PLEAS KNOW, IT HAS BECOME THE
 DETERMINATION OF THIS OFFICE TO VISIT
 SITE TO VERIFY THE INFORMATION SHOWN.
  
 ** PLEASE KNOW, ONE SET OF EACH OF THE
 PLANS SUBMITTED HAVE NOW BEEN RETAINED
 FOR FILE INCLUDING ORIGINAL PLANS.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]