| 2006-04-15 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | UNSAT |
| | 1) WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | 2) PREVIOUS NOTE #3 NOT ADDRESSED. |
| | SHT P.2 GREASE INTERCEPTOR TO BE SIZED |
| | BY WEST PALM BEACH WATER LABORATORY. |
| | SHT.P-1,P-2 SEC 1003 GREASE TRAP. |
| | CONTACT W P BEACHWATERPLANT LAB |
| | SUPERVISOR, INDUSTRIAL COORDINATOR, |
| | LYNN MASSON OFFICE 561-822-2271 |
| | E-MAIL [email protected] |
| | |
| | 3) SHT P.2 SEC 504.7.1WATER HEATER |
| | DETAIL, PAN DRAIN REQUIRED,MINIMUM |
| | SIZE 3/4", MATERIA: PVC NOT APPROVED. |
| | |
| | 4)SHT P.3 SEC 912 COMBINATION WASTE AND |
| | VENT SYSTEM. |
| | (A) SEC 1002.5 SIZE OF FIXTURE TRAP. |
| | A TRAP SHALL NOT BE LARGER THAN THE |
| | DRAINAGE PIPE INTO WHICH THE TRAP |
| | DISCHARGES. FS, FIXTURE DRAINS |
| | (B) TAB 906.1 MAXIMUM DISTANCE OF |
| | FIXTURE TRAP FROM VENT.EQUIPMENT #7, |
| | #8 ICE , SODA DISPENSER FS |
| | |
| | 5) SHT P.1PLEASE CLARIFI,FS BETWEEN |
| | HAND SINK AND SODA & ICE DISPENSER IS |
| | SHOWN IN A WALK AREA. 4'1" FROM WALL, |
| | FS ARE FOR INDIRECT WASTE, NOT TO BE |
| | USED AS A FLOOR DRAIN. |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |