 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) REVIOUS NOTE #8 NOT ADDRESSED.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 2)SHT M.2 NOTE "H" GAS FIRED DUCT
 HEATER.
 NOT INCLUDED ON GAS ISOMETRIC, 175 BTU
  
 3)SEC 409.5 EQUIPMENT SHUT OFFF VALVES.
 SHT MH.2EMERGENCY HOOD SHUT DOWN SHUT
 OFF VALVE TO BE BELOW CEILING. MANUAL
 SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWNSTREAM OF MANUAL SHUT OFF VALVE.
  
 END OF COMMENTS, QUESTIONS 561-805-6692