Plan Review Notes
Plan Review Notes For Permit 05110790
Permit Number 05110790
Review Stop E
Sequence Number 2
Notes
Date Text
2006-03-30 00:00:00IN ELEC FOR REVIEW.
 ******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL NEEDING TO BE ADDRESSED
 AND NEW COMMENTS TO CHNAGES IN PLANS
 FROM PREVIOUS PLANS SUBMITTED.
  
 * PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE END OF FIRST
 REVIEW NOTES.
  
 ************ UNSAT ************
  
  
 1)NOTE: NOTE #1 NO, PLEASE SEE PREVIOUS
 NOTE AS PLANS ORIGINALLY CAME IN
 DESIGNED UNDER THE 2001 FBC WHEN THE
 CODE IN EFFECT AT THAT TIME WAS THE
 2004. PLEASE SEE PREVIOUS NOTE MENTIONED
 TO PLEASE MAKE ALL CHANGES IN DESIGN TO
 THE 2004 FBC.
 PLEASE SEE NEW NOTES BELOW.
  
 ** PRE-REVIEW**
 PLEASE SEE PLANS STATE THE 2001
 FBC, HOWEVER AS OF OCT. 1ST, 2005 THE
 CODE HAS CHANGED TO THE 2004 FBC AND ALL
 OTHER RELEVANT CODES.
 PLEASE SEE PERMIT WAS NOT APPLIED FOR
 UNTIL NOV. 21ST, 2005
 PLEASE ADJUST ALL PLANS.
  
 2)NOTE: NOTE #2 OK.
  
 ** PRE-REVIEW**
  
 PLEASE SEE ALL SHEETS IN BOTH SETS ARE
 SEALED PHOTOCOPIES OF SIGNED PLANS.
 PLEASE SEE FS 481.221 AND FAC
 61G1-16.003 WHICH REQUIRE THE PLANS TO
 HAVE AN "ORIGINAL WET SIGNATURE AND
 DATE".
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 ONE SET MAY BE RETAINED.
  
 3)NOTE:NOTE #3 OK, HOWEVER SEE NEW
 NOTES FOR HAND DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW**
 PLEASE SEE ELECTRICAL SHEETS
 CONTAIN A TITLE BLOCK FOR AN ENGINEER.
 PLEASE KNOW, IF THIS ENGINEER IS
 RESPONSIBLE FOR DESIGN OR ELECTRICAL
 WORK ON SAID PLANS, THEN PLANS MUST BE
 SIGNED DATED AND SEALED BY SAID
 ENGINEER.
 FS 471.025
 PLEASE ALSO SEE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002 WHICH REQUIRES THE
 TITLE BLOCK FOR ENGINEER TO BE COMPLETE
 WITH ALL INFORMATION AS SET-FORTH IN THE
 LISTED FAC.
  
 4)NOTE:NOTE #4 OK.
  
 ** PRE-REVIEW**
 PLEASE SEE 600.5 FOR MISSING
 REQUIRED SIGN CIRCUIT.
  
 5)NOTE:NOTE #5 OK, HOWEVER PLEASE SEE
 THESE ARE NOW ADDED, BUT TO THE GENERAL
 RECEPTS IN DINING AREA. PLEASE KNOW,
 THESE SHOULD BE DEDICATED PER LOADS.
 PLEASE SEE210.62,220.12A,220.3(B)(7)
 CODE COMMENTARY FOLLOWING IN THE 2002
 NEC HANDBOOK.
  
 ** PRE-REVIEW**
 PLEASE SEE MISSING REQUIRED
 WINDOW OUTLETS ABOVESTORE FRONT.
 210.62.
 PLEASE SEE MIN KVA TO BE FIGURED PER
 220.12A
 THIS IS TO DISCOURAGE FLOOR RECEPTACLES
 AND UNSIGHTLY EXTENSION CORDS USED FOR
 SIGNAGE, DIPLAYS ETC WHICH ARE LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE THE WINDOW.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE THESE ARE
 STILLNOT SHOWN CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT AS REQUIRED PER 700.12E.
 PLEASE SEE CIRCUITING AS SHOWN AND
 "LOCK-OFF" DEVICE LISTED ON PANEL
 SCHEDULE DOES NOT MEET THE "EXCEPTION"
 AS NOTED.
  
 ** PRE-REVIEW**
 PLEASE SEE 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING SHOWN ON PLANS.
  
 7)NOTE: NOTE #7 OK.
  
 ** PRE-REVIEW**
 PLEASE COMPLETE SWITCH
 LEGS.SWITCH BANK ON PLANS.
 CAN NOT VERIFY AT THIS TIME.
  
 8)NOTE:NOTE #8 OK, HOWEVER SEE NEW
 NOTE FOR HAND-DRAWN ITEMS ON SIGNED AND
 SEALED PLANS.
  
 ** PRE-REVIEW **
 PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: NOTE # 9 NO. NONE SUBMITTED.
 PLEASE SEE NEW SERVICE AS SHOWN COMES
 FROM AN EXISTING SERVICE ON MAIN
 BUILDING AND ADDED LOAD TO THE EXISTING
 SERVICE MUST BE VERIFIED.
 PLEASE SEE NEW COMMENTS FOR MANY CHANGES
 ON RISER.
  
 ** PRE-REVIEW**
 PLEASE PROVIDE COMPLETE LOAD
 CALCULATION ON EXISTING SERVICE WHICH
 THIS SERVICE IS BEING TIED INTO.
 IT IS KNOWN TO THIS OFFICE THAT THE
 SERVICE AT THIS LOCATION CONTAINS LOADS
 ON SOME OF THE MAIN SERVICES WHICH ARE
 CLOSE TO EXCEEDING RATED LOADS.
 215.5,220
  
 10)NOTE: NOTE #10 NO?? PLEASE SEE A NOTE
 WAS ADDED FOR "DOWN SYSTEM BREAKER
 SERIES". THIS IS UNCLEAR AS AN AVAILABLE
 FAULT CURRENT IS NOTED AS 37,880 FROM
 FPL, YET THE SERIES RATINGS ARE NOW
 SHOWING 100K??
 PLEASE KNOW, AIC RATINGS SHALL BE STATED
 FOR NEW MAINS, NEW PANELS AND SERIES
 RATING ON BRANCH BRKRS.
 110.9,215.5
  
 ** PRE-REVIEW **PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALL-ED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
 PER 110.9/215.5
  
 11)NOTE: NOTE: 11 NO, PELASE SEE THE
 "EQUIPMENT GROUNDING CONDUCTOR" IS NOW
 REMOVED, HOWEVER MAY BE REQUIRED AS THE
 "SERVICE MAIN" IS STILL NOT SHOWN OR
 INDICATED ON PLANS.
 PLEASE KNOW, IF THE "SERVICE MAIN" FOR
 BUILDING IS LOCATED AHEAD OF GUTTER
 SHOWN, THE NEUTRAL AND EQUIPMENT
 GROUNDING CONDUCTORS SHALL NOT BE BONDED
 AFTER THE FIRST MEANS OF DICSCONNECT.A
 "FLOATING NEUTRAL" WILL BE REQUIRED.
  
 ** PRE-REVIEW**
 PLEASE SEE 250.6 , 250.24, IT
 IS NOT SHOWN IF THERE IS A "MAIN" ON THE
 LINE SIDE OF THE GUTTER SHOWN.
 THEREFORE, THE 'EQUIPMENT GROUND" SHOWN
 FROM GUTTER TO METER AND METER TO MAIN
 SHOWN, MAY BE PARALLING THE NEUTRAL.??
 CAN NOT VERIFY AT THIS TIME?
  
 12)NOTE: NOTE#12 NO, PLEASE SEE NEW
 COMMENTS AS RISER DIAGRAM HAS COMPLETELY
 CHANGED FROM PREVIOUS PLANS AND MANY
 CHANGES TO SERVICE WERE MADE.
  
 **PRE-REVIEW**
 PLEASE CORRELATE RISER WITH
 PANELS. PLEASE SEE PANEL "B" IS SHOWN AS
 MLO ON SCHEDULE, HOWEVER RISER SHOWS
 MCB.
  
 13)NOTE:NOTE #13 OK.
  
 **PRE-REVIEW**
 PLEASE SEE CONTINUOUS LOADS ARE
 SHOWN AT 125%, HOWEVER PLEASE ALSO
 INDICATE ANY LARGEST MOTORS LOADS ALSO
 @125%.
 215.3, 230.42 ETC.
  
 14)NOTE: NOTE #14 OK.
  
 ** PRE-REVIEW** PLEASE PROVIDE DETAIL
 FOR MEANS
 OF SHUT DOWN OF ALL ELECTRICAL FOR HOOD.
 NFPA-96
  
  
 ***************************************
 ************* NEW COMMENTS ***********
  
 15) NOTE: PLEASE KNOW, THESE PLANS ARE
 SIGNED DATED AND SEALED PLANS BY AN
 ENGINEER UNDER FLORIDA STATUES 471.
 PLEASE KNOW, HAND DRAWN CHANGES TO
 PLANS, FOR CIRCUITING, DESIGN, NOTES ETC
 ARE NOT PERMITTED UNDER FS 471.
 PLEASE KNOW, AN ENGINEER MAY MAKE
 CHANGES TO SAID PLANS, HOWEVER EACH AND
 EVERY ITEM IS REQUIRED TO BE SIGNED AND
 DATED AND "WHITE-OUT" ON PLANS IS NOT
 PERMITTED.
 PLEASE SEE PLANS CONATIN MANY AREAS
 WHERE CHANGES WERE MADE , SOME AREAS
 WHERE "WHITE-OUT WAS USED AND AREA WHERE
 CORRECTIONS WERE "PASTED" OVER PLANS.
 PLANS SHALL BE RE-PRINTED WITH ALL
 CORRECTIONS, SIGNED, DATED AND SEALED BY
 SAID ENGINEER OF RECORD.
 PLEASE SEE COMMENT BELOW AS COPIES OF
 PLANS ARE BEING RETAINED.
  
 16)NOTE:PLEASE CORRELATE ALL PANEL ONS
 RISER, PANEL SCHEDULES AND SEE NOTES AS
 CODE VIOLATIONS ARE SHOWN FOR NEW
 REVISIONS.
 A)PLEASE SEE RISER NOW SHOWS PANELS AS
 200A BEING FED FROM A 400A DISCONNECT
 AND 400A OCP.?? ORIG RISER SHOWED 400A
 PANELS.
 B)PLEASE SEE BOTH PANELS ARE NOW LISTED
 AS 200A ON RISER AND 225A ON PANEL
 SCHEDULES.??? ORIG PLANS INDICATED
 PANELS ON SCHEDULES AS 400A, ONLY PANEL
 "B" WAS SHOWN AS 400A MCB ON RISER, YET
 400A MLO ON SCHEDULE.
 PLEASE SEE FEEDER TO PANEL "A" STILL
 SHOWN AS 500 MCM'S WHICH ARE RATED AT
 400A'S>
 C) PLEASE SEE LOAD CALCULATIONS MENTIONS
 300A SERVICE.? PLEASE CORRELATE.
 215.5, 2002 NEC.
  
 17) NOTE: PLEASE SEE PREVIOUS REVIEW
 REQUESTED DESIGN TO MEET 2004 FBC AS
 PLANS WERE SUBMITTED AFTER 1ST OCT, 2005
 WHEN THE CODE CHANGED.
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1FOR NEW LIGHTING
 CONTROLS REQUIRED. PLEASE SUBMIT A
 METHOD, AND TIME OF DAY SCHEDULING.
 PLEASE ALSO SEE 13-415.1.ABC.1.2
  
 18) NOTE: PLEASE SEE COPY OF FLORIDA
 STATUES 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS
 FOR CODE COMPLIANCE. PLEASE KNOW, IF ANY
 OF THE SAME COMMENTS FROM THE FIRST TWO
 REVIEWS ARE NOT ADDRESSED FOR THIRD SUCH
 REVIEW, THIS OFFICE WILL HAVE NO CHOICE
 BUT TO ASSESS A 4X FEE FOR THE PLAN
 REVIEW PORTION OF THE PERMIT FEE. (30%
 OF BASE FEE X4).
 PLEASE KNOW, TO DATE THIS OFFICE HAS NOT
 BEEN CONTACTED FOR ANY QUESTIONS OR
 COMMENTS.
 ** PLEASE KNOW, ONE SET OF EACH OF THE
 PLANS SUBMITTED HAVE NOW BEEN RETAINED
 FOR FILE INCLUDING ORIGINAL PLANS.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  