| Date |
Text |
| 2006-01-30 00:00:00 | PAUL SCHMITZ |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 PLUMBING CODEPLAN REVIEW |
| | FBC 2004 FL ACESSIBILITY CODE PLAN |
| | REVIEW |
| | 1)SHT.C-S APPLICABLE CODES, FBC 2004 |
| | |
| | 2)PLANS SHALL BE ROUTED TO DBPR |
| | BUSINESS AND HOTEL DIVISION FOR |
| | REVIEW. MINIMUM 2 SETS OF PLANS |
| | SHALL BE REVIEWED AND STAMPED |
| | AND THE TWO PAGE ?WORKSHEETS? |
| | ATTACHED TO EACH SET OF PLANS |
| | PRIOR TO RESUBMITTING TO CITY OF WEST |
| | PALM BEACH |
| | FOR REVIEW. PLEASE CONTACT DBPR |
| | AT (850) 487-1395. |
| | 3)SHT.P-1,P-2 SEC 1003 GREASE TRAP. |
| | SHALL NOT BE LOCATED IN FOOD PREPREATION |
| | AREA.FOR GREASE TRAP SIZE. |
| | CONTACT W P BEACHWATERPLANT LAB |
| | SUPERVISOR, INDUSTRIAL COORDINATOR, |
| | LYNN MASSON OFFICE 561-822-2271 |
| | E-MAIL [email protected] |
| | 4)SHT P-3 WATER RISER: SHOW SOURCE |
| | OF WATER SUPPLY ANDLOCATION OF BACK |
| | FLOW PREVENTER, LOCAL ORDINANCE #2853-95 |
| | 5)WATER RISER SEC 607.3.2 THERMAL |
| | EXPANSION A MEANS OF CONTROLLING THERMAL |
| | EXPANSION SHALL BE PROVIDED. |
| | 6) SHT.P-1 SEC 606.1(4) LOCATION OF FULL |
| | OPEN VALVES. SHALL BE ON THE TOP OF |
| | EVERY DOWN FEED PIPE IN OCCUPANCIES |
| | OTHER THAN ONE AND TWO FAMILY RESIDENTAL |
| | OCCUPANCIES. |
| | 7) SHT P-3 SEC 601.1 SCOPE. TYPE OF |
| | MATERIAL FOR WATER PIPING. |
| | 8) SHT.P-3 SEC 701.1 SCOPE. TYPE OF |
| | MATERIAL FOR DRAIN WASTE AND VENT. |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |