Plan Review Notes
Plan Review Notes For Permit 05110790
Permit Number 05110790
Review Stop M
Sequence Number 1
Notes
Date Text
2005-12-13 00:00:00------------------DENIED----------------
  
 1)PAGE EQ.1 GENERAL NOTE #2 REFERS TO
 BUILDING CODE BODIES NOT APPLICABLE IN
 THIS JURISDICTION.PLEASE REFERENCE FBC
 2004.
  
 2)PAGE A.1 BUILDING PLAN SHOWS ONE HOUR
 RATED CORRIDOR TO BACK EXIT FROM DINING
 ROOM.DUCTS PENETRATING RATED ASSEMBLES
 REQUIRE FIRE DAMPERS PER FBC,M 607.5.
 PAGE M.1 SHOWS THREE DUCTS PENETRATING
 CORRIDOR WALL ASSEMBLIES.
  
 3)PAGE M.1 ROOF WORK SHOWS A COOLER
 CONDENSOR NEAR THE ROOF EDGE.A GUARD
 IS REQUIRED IF EQUIPMENT REQUIRING
 SERVICE IS LOCATED WITHIN 10' OF ROOF
 EDGE PER FBC,M 304.10.
  
 4)PAGE EQ.1 EQUIPMENT SCHEDULE #22 SHOWS
 A WALK-IN COOLER. A SEPERATE PERMIT
 APPLICATION IS REQUIRED FOR THIS WORK.
  
 5)PAGES MH.1 THRU MH.3 SHOW MECHANICAL
 HOOD AND HOOD SUPPRESSION SYSTEMS.
 SEPERATE PERMIT APPLICATIONS AND
 SUPPORTING DOCUMENTATION IS REQUIRED FOR
 EACH OF THOSE SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 RON REGUEIRO AT 561.805.6734 OR PATTY
 KRAUSS AT 561.805.6719