| Plan Review Notes For Permit 05110790 |
| Permit Number |
05110790 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-13 00:00:00 | ------------------DENIED---------------- | | | | | | 1)PAGE EQ.1 GENERAL NOTE #2 REFERS TO | | | BUILDING CODE BODIES NOT APPLICABLE IN | | | THIS JURISDICTION.PLEASE REFERENCE FBC | | | 2004. | | | | | | 2)PAGE A.1 BUILDING PLAN SHOWS ONE HOUR | | | RATED CORRIDOR TO BACK EXIT FROM DINING | | | ROOM.DUCTS PENETRATING RATED ASSEMBLES | | | REQUIRE FIRE DAMPERS PER FBC,M 607.5. | | | PAGE M.1 SHOWS THREE DUCTS PENETRATING | | | CORRIDOR WALL ASSEMBLIES. | | | | | | 3)PAGE M.1 ROOF WORK SHOWS A COOLER | | | CONDENSOR NEAR THE ROOF EDGE.A GUARD | | | IS REQUIRED IF EQUIPMENT REQUIRING | | | SERVICE IS LOCATED WITHIN 10' OF ROOF | | | EDGE PER FBC,M 304.10. | | | | | | 4)PAGE EQ.1 EQUIPMENT SCHEDULE #22 SHOWS | | | A WALK-IN COOLER. A SEPERATE PERMIT | | | APPLICATION IS REQUIRED FOR THIS WORK. | | | | | | 5)PAGES MH.1 THRU MH.3 SHOW MECHANICAL | | | HOOD AND HOOD SUPPRESSION SYSTEMS. | | | SEPERATE PERMIT APPLICATIONS AND | | | SUPPORTING DOCUMENTATION IS REQUIRED FOR | | | EACH OF THOSE SYSTEMS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | RON REGUEIRO AT 561.805.6734 OR PATTY | | | KRAUSS AT 561.805.6719 |
|