| Date |
Text |
| 2005-12-24 00:00:00 | ************ UNSAT ************ |
| | |
| | ** PLEASE SEE THIS IS A CHANGE IN |
| | OCCUPANCY AND ALL ITEMS MUST BE BROUGHT |
| | UP TO CODE. |
| | |
| | ** PLEASE ALSO SEE ADDRESSING NEEDS TO |
| | BE CORRECTED. PLEASE SEE PERMIT |
| | APPLICATION PCN USED DIRECTS ADDRESS TO |
| | 831 VILLAGE , HOWEVER PERMIT APPLICATION |
| | SHOWS 871 VILLAGE, AND PLANS ALSO SHOW |
| | 871 VILLAGE. |
| | |
| | 1)NOTE: PLEASE SEE PLANS STATE THE 2001 |
| | FBC, HOWEVER AS OF OCT. 1ST, 2005 THE |
| | CODE HAS CHANGED TO THE 2004 FBC AND ALL |
| | OTHER RELEVANT CODES. |
| | PLEASE SEE PERMIT WAS NOT APPLIED FOR |
| | UNTIL NOV. 21ST, 2005 |
| | PLEASE ADJUST ALL PLANS. |
| | |
| | 2)PLEASE SEE ALL SHEETS IN BOTH SETS ARE |
| | SEALED PHOTOCOPIES OF SIGNED PLANS. |
| | PLEASE SEE FS 481.221 AND FAC |
| | 61G1-16.003 WHICH REQUIRE THE PLANS TO |
| | HAVE AN "ORIGINAL WET SIGNATURE AND |
| | DATE". |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | ONE SET MAY BE RETAINED. |
| | |
| | 3)NOTE: PLEASE SEE ELECTRICAL SHEETS |
| | CONTAIN A TITLE BLOCK FOR AN ENGINEER. |
| | PLEASE KNOW, IF THIS ENGINEER IS |
| | RESPONSIBLE FOR DESIGN OR ELECTRICLA |
| | WORK ON SAID PLANS, THEN PLANS MUST BE |
| | SIGNED DATED AND SEALED BY SAID |
| | ENGINEER. |
| | FS 471.025 |
| | PLEASE ALSO SEE FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002 WHICH REQUIRES THE |
| | TITLE BLOCK FOR ENGINEER TO BE COMPLETE |
| | WITH ALL INFORMATION AS SET-FORTH IN THE |
| | LISTED FAC. |
| | |
| | 4)NOTE: PLEASE SEE 600.5 FOR MISSING |
| | REQUIRED SIGN CIRCUIT. |
| | |
| | 5)NOTE: PLEASE SEE MISSING REQUIRED |
| | WINDOW OUTLETS ABOVESTORE FRONT. |
| | 210.62. |
| | PLEASE SEE MIN KVA TO BE FIGURED PER |
| | 220.12A |
| | THIS IS TO DISCOURAGE FLOOR RECEPTACLES |
| | AND UNSIGHTLY EXTENSION CORDS USED FOR |
| | SIGNAGE, DIPLAYS ETC WHICH ARE LIKELY TO |
| | CAUSE PHYSICAL INJURY, RECEPTACLES MUST |
| | BE INSTALLED DIRECTLY ABOVE THE WINDOW. |
| | |
| | 6)NOTE: PLEASE SEE 700.12E WHICH |
| | REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE ADJUST CIRCUITING SHOWN ON PLANS. |
| | |
| | 7)NOTE: PLEASE COMPLETE SWITCH |
| | LEGS.SWITCH BANK ON PLANS. |
| | CAN NOT VERIFY AT THIS TIME. |
| | |
| | 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | 9)NOTE: PLEASE PROVIDE COMPLETE LOAD |
| | CALCULATION ON EXISTING SERVICE WHICH |
| | THIS SERVICE IS BEING TIED INTO. |
| | IT IS KNOWN TO THIS OFFICE THAT THE |
| | SERVICE AT THIS LOCATION CONTAINS LOADS |
| | ON SOME OF THE MAIN SERVICES WHICH ARE |
| | CLOSE TO EXCEEDING RATED LOADS. |
| | 215.5,220 |
| | |
| | 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 11)NOTE: PLEASE SEE 250.6 , 250.24, IT |
| | IS NOT SHOWN IF THERE IS A "MAIN" ON THE |
| | LINE SIDE OF THE GUTTER SHOWN. |
| | THEREFORE, THE 'EQUIPMENT GROUND" SHOWN |
| | FROM GUTTER TO METER AND METER TO MAIN |
| | SHOWN, MAY BE PARALLING THE NEUTRAL.?? |
| | CAN NOT VERIFY AT THIS TIME? |
| | |
| | 12)NOTE: PLEASE CORRELATE RISER WITH |
| | PANELS. PLEASE SEE PANEL "B" IS SHOWN AS |
| | MLO ON SCHEDULE, HOWEVER RISER SHOWS |
| | MCB. |
| | |
| | 13)NOTE: PLEASE SEE CONTINUOUS LOADS ARE |
| | SHOWN AT 125%, HOWEVER PLEASE ALSO |
| | INDICATE ANY LARGEST MOTORS LOADS ALSO |
| | @125%. |
| | 215.3, 230.42 ETC. |
| | |
| | 14)NOTE: PLEASE PROVIDE DETAIL FOR MEANS |
| | OF SUT DOWN OF ALL ELECTRICAL FOR HOOD. |
| | NFPA-96 |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |