Plan Review Notes
Plan Review Notes For Permit 05110790
Permit Number 05110790
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110790
 ADD: 871 VILLAGE BLVD
 CONT: 3D CONSTRUCTIO
 TEL: (407)383-9797
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SIGNATURE NOT TO BE COPIES BUT
 ORIGINAL!!!!!!!!
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.(2004)
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
  
 4)1609.3 BASIC WIND SPEED.
 THE BASIC WIND SPEED IN MILES PER HOUR,
 FOR THE DEVELOPMENT OF WIND LOADS, SHALL
 BE DETERMINED FROM FIGURE 1609 . BASIC
 WIND SPEED FOR THE SPECIAL WIND REGIONS
 INDICATED, NEAR MOUNTAINOUS TERRAIN AND
 NEAR GORGES SHALL BE IN ACCORDANCE WITH
 LOCAL JURISDICTION REQUIREMENTS. THE
 EXACT LOCATION OF WIND SPEED LINES SHALL
 BE ESTABLISHED BY LOCAL ORDINANCE USING
 RECOGNIZED PHYSICAL LAND MARKS SUCH AS
 MAJOR ROADS, CANALS, RIVERS AND LAKE
 SHORES, WHEREVER POSSIBLE.
 WEST PALM BEACH IS LOCATED IN A 140 MPH
 WIND ZONE 3 SECOND GUST.
  
 5)(2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
 IT APPEARS THAT ADDITIONAL AIR HANDLERS
  
 ARE BEING INSTALLED ON THE ROOF, A
 LETTERWILL BE REQUIRED FROM AN
 ENGINEER FOR THE ADDITIONAL POINT
 LOADING OF THE BAR JOIST, ALSO WILL ANY
 BAR JOIST BE CUT?
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) PREMANUFACTURED A/C ROOF STANDS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7)1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
 8) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 10) MECHANICAL DESIGNER TO SIGN & SEAL
 ENERGY CALC13-103.2 DETAILS, PLANS AND
 SPECIFICATIONS.
 PLANS AND SPECIFICATIONS SHALL BE
 SUBMITTED WITH EACH APPLICATION FOR A
 BUILDING PERMIT. ENERGY CODE
 CALCULATIONS SHALL BE MADE A PART OF THE
 PLANS AND SPECIFICATIONS OF THE
 BUILDING. THE BUILDING OFFICIAL SHALL
 REQUIRE, SUBJECT TO THE EXCEPTIONS IN
 SECTION 481.229, FLORIDA STATUTES , AND
 SECTION 471.003, FLORIDA STATUTES , THAT
 PLANS AND SPECIFICATIONS BE PREPARED BY
 AN ENGINEER OR ARCHITECT LICENSED TO
 PRACTICE IN THE STATE OF FLORIDA. THE
 PLANS AND SPECIFICATIONS, INCLUDING THE
 ENERGY CODE CALCULATIONS, SHALL SHOW, IN
 SUFFICIENT DETAIL, ALL PERTINENT DATA
 AND FEATURES OF THE BUILDING AND THE
 EQUIPMENT AND SYSTEMS AS HEREIN GOVERNED
 INCLUDING, BUT NOT LIMITED TO: DESIGN
 CRITERIA, EXTERIOR ENVELOPE COMPONENT
 MATERIALS, U -VALUES OF THE ENVELOPE
 SYSTEMS, R -VALUES OF INSULATING
 MATERIALS, SIZE AND TYPE OF APPARATUS
 AND EQUIPMENT, EQUIPMENT AND SYSTEMS
 CONTROLS AND OTHER PERTINENT DATA TO
 INDICATE CONFORMANCE WITH THE
 REQUIREMENTS OF THE CODE
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026