Plan Review Notes
Plan Review Notes For Permit 05110729
Permit Number 05110729
Review Stop P
Sequence Number 2
Notes
Date Text
2006-07-22 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 PROVISO: BUILDING FOUNDATION ONLY.
  
 NEW COMMENTS, APPLICATION #06030729
 *** INDICATES NEW COMMENT.
 1) PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
 REMOVE VOIDED SHEETS, INCLUDE IN
 RESUBMITTAL, IN A SEPERATE PACKAGE.
  
 *** PLEASE PROVIDE A TRANSMITTAL SHEET
 ADDRESSING PLAN REVIEW COMMENTS.
 *** SHEET NUMBERS HAVE CHANGED
 2) SHT A-2.04
 PLUMBING FIXTURE REQUIRMENTS:
 BUSINESS OCCUPANCY NOT LISTED.
 EACH TENANT SPACE TO COMPLY WITH TABLE
 403.1 FOR MINIMUM FACILITIES.
 ONE W/C & LAV, ONE SAFTEY SHOWER, ONE
 DRINKING FOUNTAIN, ONE S/S.
 3)SHT A-2.04
 PROVIDE A ELEVATION DETAIL OF TOILET
 ROOMS AND DRINK FOUNTAINS WITH
 DIMENSIONS.
 11-4.22 TOILET ROOMS.
 11-4.22.1 MINIMUM NUMBER.
 TOILET FACILITIES REQUIRED TO BE
 ACCESSIBLE BY SECTION 11-4.1 SHALL
 COMPLY WITH SECTION 11-4.22. ACCESSIBLE
 TOILET ROOMS SHALL BE ON AN ACCESSIBLE
 ROUTE.
 11-4.22.2 DOORS.
 *** SHT A-3.01 DOOR SWINGS INTO TURNING
 CIRCLE.
 (1)ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 11-4.22.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN SECTIONS 11-4.22.4,
 11-4.22.5, 11-4.22.6 AND 11-4.22.7 SHALL
 BE ON AN ACCESSIBLE ROUTE. AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH SECTION 11-4.2.3 SHALL BE PROVIDED
 WITHIN AN ACCESSIBLE TOILET ROOM. THE
 CLEAR FLOOR SPACE AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE
 TURNING SPACE MAY OVERLAP.
 11-4.22.6 LAVATORIES AND MIRRORS.
 IF LAVATORIES AND MIRRORS ARE PROVIDED,
 THEN AT LEAST ONE OF EACH SHALL COMPLY
 WITH SECTION 11-4.19.
 11-4.22.7 CONTROLS AND DISPENSERS.
 IF CONTROLS, DISPENSERS, RECEPTACLES, OR
 OTHER EQUIPMENT ARE PROVIDED, THEN AT
 LEAST ONE OF EACH SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL COMPLY WITH
 SECTION 11-4.27.
 11-4.23 BATHROOMS, BATHING FACILITIES
 AND SHOWER ROOMS.
 11-4.23.1 MINIMUM NUMBER.
 BATHROOMS, BATHING FACILITIES, OR SHOWER
 ROOMS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.23 AND SHALL BE ON AN ACCESSIBLE
 ROUTE.
 11-4.23.2 DOORS.
 DOORS TO ACCESSIBLE BATHROOMS SHALL
 COMPLY WITH SECTION 11-4.13. DOORS SHALL
 NOT SWING INTO THE FLOOR SPACE REQUIRED
 FOR ANY FIXTURE. IF ONLY A TOILET ROOM
 IS PROVIDED AT GRADE LEVEL, SUCH TOILET
 ROOM SHALL HAVE A CLEAR OPENING OF NOT
 LESS THAN 29 INCHES (737 MM).
 11-4.23.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN SECTIONS 11-4.23.4,
 11-4.23.5, 11-4.23.6, 11-4.23.7,
 11-4.23.8 AND 11-4.23.9 SHALL BE ON AN
 ACCESSIBLE ROUTE. AN UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH SECTION
 11-4.2.3 SHALL BE PROVIDED WITHIN AN
 ACCESSIBLE BATHROOM. THE CLEAR FLOOR
 SPACES AT FIXTURES AND CONTROLS, THE
 ACCESSIBLE ROUTE, AND THE TURNING SPACE
 MAY OVERLAP.
 4) SHTS P0.1 PLUMBING GENERAL NOTES #6
 CLARIFI USE OF DUCTILE IRON PIPE LESS
 THAN 2 FEET UNDER GROUND.
 *** SHT P0.1 NOTE #6 DUCTILE IRON NOT
 ADDRESSED.
 PLUMBING FIXTURE SCHEDULE P-42, CLARIFI
 TYPE OF SHOWER, SAFETY OR PERSONEL?
 P-62B HOSE BIBB, PROVIDE VACUM BREAKER.
 *** P-62B VACUM BREAKER NOT ADDRESSED.
 5) SHT P2.3 PROVIDE A ISOMETRIC DRAWING
 FOR BUSINESS OFFICE, SANITARY AND WATER
 PIPEING. INCLUDE DRINKING FOUNTAIN,
 EMERGENCY SHOWER AND EYE WASH.
 *** SHT P2.3 DOMESTIC WATER ISOMETRIC.
 SHOCK ARRESTORS LOCATED AT TOP OF RISER
 NOT PER MANFACTURE INSTALLATIONS
 INSTRUCTIONS.
 *** SHT P2.3WATER HEATER, DETAIL NOT
 PROVIDED AS INDICATED ON SHT P0.1
 SEC 607.3 PROVIDE A MEANS OF CONTROLING
 THERMAL EXPANSION FOR WATER HEATER.
 WATER SUPPLY NOT SHOWN FOR SAFTEY
 SHOWER.
 SANITARY WASTE ISOMETRIC:ICE MACHINE
 DRAIN NOT SHOWN.
 *** SHT. L-3.03 IRRIGATION: SEC 316
 SPRINKLER HEADS SHALL NOT BE INSTALLED
 WITHIN 12" OF THE BUILDING
  
 END OF COMMENTS QUESTIONS,561-8056692