2006-07-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110729
 ADD:4300 N FLAGLER DR
 CONT: ROONEY CENTEX CONSTRUCTION
 TEL: (561)478-0381
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 -----NOTE-----
  
 THIS PERMIT APPLICATION IS FOR SITE
 CLEARING AND SITE UTILITIES AND
 FOUNDATION OF THE MTC (MARINE
 TECHNOLOGIES CENTER) BUILDING.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY.PLEASE REMOVE THE
 "VOID" SHEETS AND STAPLE ONE SET
 TOGETHER.A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 3) BUILDING PROVISO:
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4) COMMENT# 4 TO BE ADDRESSED UNDER THE
 BUILDING PERMIT.
  
 5) COMMENT# 5 TO BE ADDRESSED UNDER THE
 BUILDING PERMIT.
  
 6A)COMMENT TO BE ADDRESSED UNDER THE
 BUILDING PERMIT. OFFICE BAY# 1 SECOND
 FLOOR SQ FT APPEARS TO BE 978 SQ FT A
 TRUE SECOND FLOOR.
  
 6B) COMMENT TO BE ADDRESSED UNDER THE
 BUILDING PERMIT.
  
 6C) COMPLIED.
  
 7)COMMENT TO BE ADDRESSED UNDER THE
 BUILDING PERMIT. OFFICE SECOND FLOOR
 AREA APPROXIMATELY 978 SQ FT.OR AN
 OCCUPANT LOAD OF 10, THUS REQUIRING THE
 ENCLOSED STAIR.1019.1 THE EXCEPTION IS
 LESS THAN 10.
 7B) TO BE ADDRESSED UNDER THE BUILDING
 PERMIT. THE OTHER ISSUE THAT I WAS
 REFERING TO WAS VERTICAL ACCESSIBILITY,
 I QUESTIONED IF ANY OF THE 2ND FLOOR WAS
 TO BE STORAGE, PLANS INDICATE A
 CONFERENCE ROOM WITH 8 CHAIRS AND 2
 OFFICES WITH A TOTAL OF 6 CHAIRS OR A
 POSSIBLE 14 PEOPLE.
 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR
 FACILITIES: NEW CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY
 TO BUILDINGS, STRUCTURES, OR FACILITIES
 WHICH WERE EITHER UNDER CONSTRUCTION OR
 UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1, 1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE AND BELOW THE OCCUPIABLE
 GRADE LEVEL, REGARDLESS OF WHETHER THE
 CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR
 FACILITY, EXCEPT: (1) ELEVATOR PITS,
 ELEVATOR PENTHOUSES, MECHANICAL ROOMS,
 PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE
 PITS AND PLATFORMS; (2) UNOCCUPIABLE
 SPACES, SUCH AS ROOMS, ENCLOSED SPACES,
 AND STORAGE SPACES THAT ARE NOT DESIGNED
 FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND
 (3) OCCUPIABLE SPACES AND ROOMS THAT ARE
 NOT OPEN TO THE PUBLIC AND THAT HOUSE NO
 MORE THAN FIVE PERSONS INCLUDING, BUT
 NOT LIMITED TO, EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS. HOWEVER AS
 PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND
 FACILITIES MUST, AT A MINIMUM, COMPLY
 WITH THE REQUIREMENTS OF THE ADAAG.
 THEREFORE, FACILITIES SUBJECT TO THE
 ADAAG MAY BE REQUIRED TO PROVIDE
 VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5) OF
 THIS CODE.
  
 8) COMPLIED.
  
 9) TO BE ADDRESSED UNDER BUILDING
 PERMIT.
  
 10) TO BE ADDRESSED UNDER THE BUILDING
 PERMIT.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) BUILDING PROVISO:
 PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".
  
 14) 2ND REQUEST,
 S1-S2 MISSING INFORMATION, ANCHOR
 BOLT DESCRIPTION, SIZE LENGTH AND GRADE
 OF STEEL.BUTLERNOTE " FOUNDATION
 DESIGN AND ANCHOR BOLTS, NUTS AND
 WASHERS ARE NOT FURNISHED BY BUTLER.
 PROPER EMBEDMENT LENGTH MUST BE DESIGNED
 BY THE FOUNDATION DESIGN ENGINEER.
 GROND FLOOR ENGINEERING PROVIDED A
 RESPONCE SHEET WITH CALCULATION,
 PROVIDING (3) SIGNED BUT NOT SEALED NOR
 DATED DOCUMENTS.
  
 15) SAME AS COMMENT# 14.
  
 16) SECOND REQUESST (2) SETS OF THE
 BUTLER PLANS WILL BE RETAINED FOR
 POSSIBLE SUBMITTAL TO THE STATE BOARD OF
 ENGINEERS.
 BUTLER LAYOUT SHEETS ARE COPIES OF THE
 ENGINEERS SIGNATURE, NOT ORIGINALS,
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 17) PLANS MAY HAVE SEAL ON SOME PAGES SO
 LIGHT THE EMBOSSED INFORMATION IS
 ELLIGABLE.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20-23) TO BE ADDRESSED UNDER THE
 BUILDING PERMIT.
  
 24) 2ND REQUEST,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  