| 2006-07-25 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05110729 |
| | ADD:4300 N FLAGLER DR |
| | CONT: ROONEY CENTEX CONSTRUCTION |
| | TEL: (561)478-0381 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | -----NOTE----- |
| | |
| | THIS PERMIT APPLICATION IS FOR SITE |
| | CLEARING AND SITE UTILITIES AND |
| | FOUNDATION OF THE MTC (MARINE |
| | TECHNOLOGIES CENTER) BUILDING. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY.PLEASE REMOVE THE |
| | "VOID" SHEETS AND STAPLE ONE SET |
| | TOGETHER.A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2)BUILDING PROVISO: |
| | 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 3) BUILDING PROVISO: |
| | 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 4) COMMENT# 4 TO BE ADDRESSED UNDER THE |
| | BUILDING PERMIT. |
| | |
| | 5) COMMENT# 5 TO BE ADDRESSED UNDER THE |
| | BUILDING PERMIT. |
| | |
| | 6A)COMMENT TO BE ADDRESSED UNDER THE |
| | BUILDING PERMIT. OFFICE BAY# 1 SECOND |
| | FLOOR SQ FT APPEARS TO BE 978 SQ FT A |
| | TRUE SECOND FLOOR. |
| | |
| | 6B) COMMENT TO BE ADDRESSED UNDER THE |
| | BUILDING PERMIT. |
| | |
| | 6C) COMPLIED. |
| | |
| | 7)COMMENT TO BE ADDRESSED UNDER THE |
| | BUILDING PERMIT. OFFICE SECOND FLOOR |
| | AREA APPROXIMATELY 978 SQ FT.OR AN |
| | OCCUPANT LOAD OF 10, THUS REQUIRING THE |
| | ENCLOSED STAIR.1019.1 THE EXCEPTION IS |
| | LESS THAN 10. |
| | 7B) TO BE ADDRESSED UNDER THE BUILDING |
| | PERMIT. THE OTHER ISSUE THAT I WAS |
| | REFERING TO WAS VERTICAL ACCESSIBILITY, |
| | I QUESTIONED IF ANY OF THE 2ND FLOOR WAS |
| | TO BE STORAGE, PLANS INDICATE A |
| | CONFERENCE ROOM WITH 8 CHAIRS AND 2 |
| | OFFICES WITH A TOTAL OF 6 CHAIRS OR A |
| | POSSIBLE 14 PEOPLE. |
| | 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR |
| | FACILITIES: NEW CONSTRUCTION. |
| | THIS EDITION OF THE CODE DOES NOT APPLY |
| | TO BUILDINGS, STRUCTURES, OR FACILITIES |
| | WHICH WERE EITHER UNDER CONSTRUCTION OR |
| | UNDER CONTRACT FOR CONSTRUCTION ON |
| | OCTOBER 1, 1997. |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | STRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE AND BELOW THE OCCUPIABLE |
| | GRADE LEVEL, REGARDLESS OF WHETHER THE |
| | CODE REQUIRES AN ELEVATOR TO BE |
| | INSTALLED IN SUCH BUILDING, STRUCTURE OR |
| | FACILITY, EXCEPT: (1) ELEVATOR PITS, |
| | ELEVATOR PENTHOUSES, MECHANICAL ROOMS, |
| | PIPING OR EQUIPMENT CATWALKS, AND |
| | AUTOMOBILE LUBRICATION AND MAINTENANCE |
| | PITS AND PLATFORMS; (2) UNOCCUPIABLE |
| | SPACES, SUCH AS ROOMS, ENCLOSED SPACES, |
| | AND STORAGE SPACES THAT ARE NOT DESIGNED |
| | FOR HUMAN OCCUPANCY, FOR PUBLIC |
| | ACCOMMODATIONS, OR FOR WORK AREAS; AND |
| | (3) OCCUPIABLE SPACES AND ROOMS THAT ARE |
| | NOT OPEN TO THE PUBLIC AND THAT HOUSE NO |
| | MORE THAN FIVE PERSONS INCLUDING, BUT |
| | NOT LIMITED TO, EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. HOWEVER AS |
| | PROVIDED IN SECTION 553.509, FLORIDA |
| | STATUTES, BUILDINGS, STRUCTURES, AND |
| | FACILITIES MUST, AT A MINIMUM, COMPLY |
| | WITH THE REQUIREMENTS OF THE ADAAG. |
| | THEREFORE, FACILITIES SUBJECT TO THE |
| | ADAAG MAY BE REQUIRED TO PROVIDE |
| | VERTICAL ACCESS TO AREAS OTHERWISE |
| | EXEMPT UNDER SECTION 11-4.1.3 (5) OF |
| | THIS CODE. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) TO BE ADDRESSED UNDER BUILDING |
| | PERMIT. |
| | |
| | 10) TO BE ADDRESSED UNDER THE BUILDING |
| | PERMIT. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) BUILDING PROVISO: |
| | PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE REQUIRES |
| | AN ADDITIONAL 6". |
| | |
| | 14) 2ND REQUEST, |
| | S1-S2 MISSING INFORMATION, ANCHOR |
| | BOLT DESCRIPTION, SIZE LENGTH AND GRADE |
| | OF STEEL.BUTLERNOTE " FOUNDATION |
| | DESIGN AND ANCHOR BOLTS, NUTS AND |
| | WASHERS ARE NOT FURNISHED BY BUTLER. |
| | PROPER EMBEDMENT LENGTH MUST BE DESIGNED |
| | BY THE FOUNDATION DESIGN ENGINEER. |
| | GROND FLOOR ENGINEERING PROVIDED A |
| | RESPONCE SHEET WITH CALCULATION, |
| | PROVIDING (3) SIGNED BUT NOT SEALED NOR |
| | DATED DOCUMENTS. |
| | |
| | 15) SAME AS COMMENT# 14. |
| | |
| | 16) SECOND REQUESST (2) SETS OF THE |
| | BUTLER PLANS WILL BE RETAINED FOR |
| | POSSIBLE SUBMITTAL TO THE STATE BOARD OF |
| | ENGINEERS. |
| | BUTLER LAYOUT SHEETS ARE COPIES OF THE |
| | ENGINEERS SIGNATURE, NOT ORIGINALS, |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 17) PLANS MAY HAVE SEAL ON SOME PAGES SO |
| | LIGHT THE EMBOSSED INFORMATION IS |
| | ELLIGABLE. |
| | |
| | 18) COMPLIED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20-23) TO BE ADDRESSED UNDER THE |
| | BUILDING PERMIT. |
| | |
| | 24) 2ND REQUEST, |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |