| Date |
Text |
| 2006-05-13 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | |
| | UNSAT |
| | 1) PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT PLUMBING |
| | PLANS. |
| | |
| | 2) SHT A-2.04 |
| | PLUMBING FIXTURE REQUIRMENTS: |
| | BUSINESS OCCUPANCY NOT LISTED. |
| | EACH TENANT SPACE TO COMPLY WITH TABLE |
| | 403.1 FOR MINIMUM FACILITIES. |
| | ONE W/C & LAV, ONE SAFTEY SHOWER, ONE |
| | DRINKING FOUNTAIN, ONE S/S. |
| | |
| | 3)SHT A-2.04 |
| | PROVIDE A ELEVATION DETAIL OF TOILET |
| | ROOMS AND DRINK FOUNTAINS WITH |
| | DIMENSIONS. |
| | 11-4.22 TOILET ROOMS. |
| | 11-4.22.1 MINIMUM NUMBER. |
| | TOILET FACILITIES REQUIRED TO BE |
| | ACCESSIBLE BY SECTION 11-4.1 SHALL |
| | COMPLY WITH SECTION 11-4.22. ACCESSIBLE |
| | TOILET ROOMS SHALL BE ON AN ACCESSIBLE |
| | ROUTE. |
| | 11-4.22.2 DOORS. |
| | (1)ALL DOORS TO ACCESSIBLE TOILET ROOMS |
| | SHALL COMPLY WITH SECTION 11-4.13. DOORS |
| | SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE. |
| | 11-4.22.3 CLEAR FLOOR SPACE. |
| | THE ACCESSIBLE FIXTURES AND CONTROLS |
| | REQUIRED IN SECTIONS 11-4.22.4, |
| | 11-4.22.5, 11-4.22.6 AND 11-4.22.7 SHALL |
| | BE ON AN ACCESSIBLE ROUTE. AN |
| | UNOBSTRUCTED TURNING SPACE COMPLYING |
| | WITH SECTION 11-4.2.3 SHALL BE PROVIDED |
| | WITHIN AN ACCESSIBLE TOILET ROOM. THE |
| | CLEAR FLOOR SPACE AT FIXTURES AND |
| | CONTROLS, THE ACCESSIBLE ROUTE, AND THE |
| | TURNING SPACE MAY OVERLAP. |
| | 11-4.22.6 LAVATORIES AND MIRRORS. |
| | IF LAVATORIES AND MIRRORS ARE PROVIDED, |
| | THEN AT LEAST ONE OF EACH SHALL COMPLY |
| | WITH SECTION 11-4.19. |
| | 11-4.22.7 CONTROLS AND DISPENSERS. |
| | IF CONTROLS, DISPENSERS, RECEPTACLES, OR |
| | OTHER EQUIPMENT ARE PROVIDED, THEN AT |
| | LEAST ONE OF EACH SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL COMPLY WITH |
| | SECTION 11-4.27. |
| | 11-4.23 BATHROOMS, BATHING FACILITIES |
| | AND SHOWER ROOMS. |
| | 11-4.23.1 MINIMUM NUMBER. |
| | BATHROOMS, BATHING FACILITIES, OR SHOWER |
| | ROOMS REQUIRED TO BE ACCESSIBLE BY |
| | SECTION 11-4.1 SHALL COMPLY WITH SECTION |
| | 11-4.23 AND SHALL BE ON AN ACCESSIBLE |
| | ROUTE. |
| | 11-4.23.2 DOORS. |
| | DOORS TO ACCESSIBLE BATHROOMS SHALL |
| | COMPLY WITH SECTION 11-4.13. DOORS SHALL |
| | NOT SWING INTO THE FLOOR SPACE REQUIRED |
| | FOR ANY FIXTURE. IF ONLY A TOILET ROOM |
| | IS PROVIDED AT GRADE LEVEL, SUCH TOILET |
| | ROOM SHALL HAVE A CLEAR OPENING OF NOT |
| | LESS THAN 29 INCHES (737 MM). |
| | 11-4.23.3 CLEAR FLOOR SPACE. |
| | THE ACCESSIBLE FIXTURES AND CONTROLS |
| | REQUIRED IN SECTIONS 11-4.23.4, |
| | 11-4.23.5, 11-4.23.6, 11-4.23.7, |
| | 11-4.23.8 AND 11-4.23.9 SHALL BE ON AN |
| | ACCESSIBLE ROUTE. AN UNOBSTRUCTED |
| | TURNING SPACE COMPLYING WITH SECTION |
| | 11-4.2.3 SHALL BE PROVIDED WITHIN AN |
| | ACCESSIBLE BATHROOM. THE CLEAR FLOOR |
| | SPACES AT FIXTURES AND CONTROLS, THE |
| | ACCESSIBLE ROUTE, AND THE TURNING SPACE |
| | MAY OVERLAP. |
| | 4) SHTS P0.1 PLUMBING GENERAL NOTES #6 |
| | CLARIFI USE OF DUCTILE IRON PIPE LESS |
| | THAN 2 FEET UNDER GROUND. |
| | PLUMBING FIXTURE SCHEDULE P-42, CLARIFI |
| | TYPE OF SHOWER, SAFETY OR PERSONEL? |
| | P-62B HOSE BIBB, PROVIDE VACUM BREAKER. |
| | 5) SHT P2.3 PROVIDE A ISOMETRIC DRAWING |
| | FOR BUSINESS OFFICE, SANITARY AND WATER |
| | PIPEING. INCLUDE DRINKING FOUNTAIN, |
| | EMERGENCY SHOWER AND EYE WASH. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |