Plan Review Notes
Plan Review Notes For Permit 05110729
Permit Number 05110729
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-13 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1) PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 2) SHT A-2.04
 PLUMBING FIXTURE REQUIRMENTS:
 BUSINESS OCCUPANCY NOT LISTED.
 EACH TENANT SPACE TO COMPLY WITH TABLE
 403.1 FOR MINIMUM FACILITIES.
 ONE W/C & LAV, ONE SAFTEY SHOWER, ONE
 DRINKING FOUNTAIN, ONE S/S.
  
 3)SHT A-2.04
 PROVIDE A ELEVATION DETAIL OF TOILET
 ROOMS AND DRINK FOUNTAINS WITH
 DIMENSIONS.
 11-4.22 TOILET ROOMS.
 11-4.22.1 MINIMUM NUMBER.
 TOILET FACILITIES REQUIRED TO BE
 ACCESSIBLE BY SECTION 11-4.1 SHALL
 COMPLY WITH SECTION 11-4.22. ACCESSIBLE
 TOILET ROOMS SHALL BE ON AN ACCESSIBLE
 ROUTE.
 11-4.22.2 DOORS.
 (1)ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 11-4.22.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN SECTIONS 11-4.22.4,
 11-4.22.5, 11-4.22.6 AND 11-4.22.7 SHALL
 BE ON AN ACCESSIBLE ROUTE. AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH SECTION 11-4.2.3 SHALL BE PROVIDED
 WITHIN AN ACCESSIBLE TOILET ROOM. THE
 CLEAR FLOOR SPACE AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE
 TURNING SPACE MAY OVERLAP.
 11-4.22.6 LAVATORIES AND MIRRORS.
 IF LAVATORIES AND MIRRORS ARE PROVIDED,
 THEN AT LEAST ONE OF EACH SHALL COMPLY
 WITH SECTION 11-4.19.
 11-4.22.7 CONTROLS AND DISPENSERS.
 IF CONTROLS, DISPENSERS, RECEPTACLES, OR
 OTHER EQUIPMENT ARE PROVIDED, THEN AT
 LEAST ONE OF EACH SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL COMPLY WITH
 SECTION 11-4.27.
 11-4.23 BATHROOMS, BATHING FACILITIES
 AND SHOWER ROOMS.
 11-4.23.1 MINIMUM NUMBER.
 BATHROOMS, BATHING FACILITIES, OR SHOWER
 ROOMS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.23 AND SHALL BE ON AN ACCESSIBLE
 ROUTE.
 11-4.23.2 DOORS.
 DOORS TO ACCESSIBLE BATHROOMS SHALL
 COMPLY WITH SECTION 11-4.13. DOORS SHALL
 NOT SWING INTO THE FLOOR SPACE REQUIRED
 FOR ANY FIXTURE. IF ONLY A TOILET ROOM
 IS PROVIDED AT GRADE LEVEL, SUCH TOILET
 ROOM SHALL HAVE A CLEAR OPENING OF NOT
 LESS THAN 29 INCHES (737 MM).
 11-4.23.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN SECTIONS 11-4.23.4,
 11-4.23.5, 11-4.23.6, 11-4.23.7,
 11-4.23.8 AND 11-4.23.9 SHALL BE ON AN
 ACCESSIBLE ROUTE. AN UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH SECTION
 11-4.2.3 SHALL BE PROVIDED WITHIN AN
 ACCESSIBLE BATHROOM. THE CLEAR FLOOR
 SPACES AT FIXTURES AND CONTROLS, THE
 ACCESSIBLE ROUTE, AND THE TURNING SPACE
 MAY OVERLAP.
 4) SHTS P0.1 PLUMBING GENERAL NOTES #6
 CLARIFI USE OF DUCTILE IRON PIPE LESS
 THAN 2 FEET UNDER GROUND.
 PLUMBING FIXTURE SCHEDULE P-42, CLARIFI
 TYPE OF SHOWER, SAFETY OR PERSONEL?
 P-62B HOSE BIBB, PROVIDE VACUM BREAKER.
 5) SHT P2.3 PROVIDE A ISOMETRIC DRAWING
 FOR BUSINESS OFFICE, SANITARY AND WATER
 PIPEING. INCLUDE DRINKING FOUNTAIN,
 EMERGENCY SHOWER AND EYE WASH.
  
 END OF COMMENTS, QUESTIONS 561-805-6692