| 2006-06-01 00:00:00 | ***DENIED*** |
| | |
| | PLANS HAVE BEEN SUBMITTED FOR PERMITTING |
| | FOR FOUNDATION, SITE CLEARING AND SITE |
| | UTILITIES ONLY. |
| | |
| | 1) ELECTRONIC SUPERVISION AND CHAIN WITH |
| | LOCK IS REQUIRED FOR SECURING OF DOUBLE |
| | CHECK DETECTOR ASSEMBLY. SHT C-20. |
| | |
| | 2) FIRE DEPARTMENT CONNECTIONS SHALL BE |
| | NO FURTHER THAN 150' FROM A FIRE |
| | HYDRANT. |
| | |
| | 3) FIRE HYDRANTS ARE TO BE WET AND |
| | OPERATIONAL PRIOR TO, DURING AND AFTER |
| | CONSTRUCTION. |
| | |
| | 4) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | PLEASE PROVIDE NOTE ON ARCHITECTUAL |
| | SHEETS WHEN SUBMITTED FOR PERMIT. |
| | |
| | 5) IN ADDITION TO ALL APPLICABLE |
| | BUILDING CODES, LIFE SAFETY SHALL COMPLY |
| | WITH NFPA 101, 2003 EDITION. |
| | |
| | 6) ABOVE GROUND FIRE SPRINKLER WORK |
| | SHALL COMPLY WITH NFPA 13, 2002 EDITION. |
| | SHT FP0.1, NOTE #1. |
| | |
| | 7) SUITABLE ACCESS SHALL BE PROVIDED FOR |
| | EMERGENCY VEHICLES, AND ACCESS, WATER |
| | SUPPLY TO COMPLY WITH NFPA 1, 2003 |
| | EDITION, CHAPTER 18. |
| | |
| | 8) NO FIRE LINES SHALL BE LOCATED |
| | BENEATH BUILDINGS OR STRUCTURES. |
| | |
| | 9) ADDRESSING TO MEET ALL LOCAL |
| | REQUIREMENTS FOR COMMERCIAL BUILDINGS, |
| | AND SHALL BE AT LEAST 6" IN HEIGHT AND |
| | CONTRASTING TO THE BACKGROUND. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |