Plan Review Notes
Plan Review Notes For Permit 05110729
Permit Number 05110729
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-01 00:00:00***DENIED***
  
 PLANS HAVE BEEN SUBMITTED FOR PERMITTING
 FOR FOUNDATION, SITE CLEARING AND SITE
 UTILITIES ONLY.
  
 1) ELECTRONIC SUPERVISION AND CHAIN WITH
 LOCK IS REQUIRED FOR SECURING OF DOUBLE
 CHECK DETECTOR ASSEMBLY. SHT C-20.
  
 2) FIRE DEPARTMENT CONNECTIONS SHALL BE
 NO FURTHER THAN 150' FROM A FIRE
 HYDRANT.
  
 3) FIRE HYDRANTS ARE TO BE WET AND
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
 PLEASE PROVIDE NOTE ON ARCHITECTUAL
 SHEETS WHEN SUBMITTED FOR PERMIT.
  
 5) IN ADDITION TO ALL APPLICABLE
 BUILDING CODES, LIFE SAFETY SHALL COMPLY
 WITH NFPA 101, 2003 EDITION.
  
 6) ABOVE GROUND FIRE SPRINKLER WORK
 SHALL COMPLY WITH NFPA 13, 2002 EDITION.
 SHT FP0.1, NOTE #1.
  
 7) SUITABLE ACCESS SHALL BE PROVIDED FOR
 EMERGENCY VEHICLES, AND ACCESS, WATER
 SUPPLY TO COMPLY WITH NFPA 1, 2003
 EDITION, CHAPTER 18.
  
 8) NO FIRE LINES SHALL BE LOCATED
 BENEATH BUILDINGS OR STRUCTURES.
  
 9) ADDRESSING TO MEET ALL LOCAL
 REQUIREMENTS FOR COMMERCIAL BUILDINGS,
 AND SHALL BE AT LEAST 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  