Plan Review Notes
Plan Review Notes For Permit 05110729
Permit Number 05110729
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-29 00:00:00 
 THIS REVIEW IS FOR CONDUIT INSTALLATION
 ONLY, AND IS NOT A REVIEW FOR THE
 ELECTRIC EQUIPMENT THAT IS SHOWN
 DIAGRAMMATICALLY, MAINS, PANELS OR POWER
 POINTS.
  
  
 MSB-1 SHOWS A PRELIMINARY LOCATION IN
 THE NORTH ELECTRIC ROOM AT COLUMN LINE
 #5. PLEASE BE ADVISED THAT THIS ROOM
 WOULD NOT BEET EGRESS REQUIREMENTS OF
 110.26(C)(2) FOR A 1200 AMP EQUIPMENT:
  
 LARGE EQUIPMENT. FOR EQUIPMENT RATED
 1200 AMPERES OR MORE AND OVER 1.8 M (6
 FT) WIDE THAT CONTAINS OVERCURRENT
 DEVICES, SWITCHING DEVICES, OR CONTROL
 DEVICES, THERE SHALL BE ONE ENTRANCE TO
 THE REQUIRED WORKING SPACE NOT LESS THAN
 610 MM (24 IN.) WIDE AND 2.0 M (61/2 FT)
 HIGH AT EACH END OF THE WORKING SPACE.
 WHERE THE ENTRANCE HAS A PERSONNEL
 DOOR(S), THE DOOR(S) SHALL OPEN IN THE
 DIRECTION OF EGRESS AND BE EQUIPPED WITH
 PANIC BARS, PRESSURE PLATES, OR OTHER
 DEVICES THAT ARE NORMALLY LATCHED BUT
 OPEN UNDER SIMPLE PRESSURE.
  
 ALSO BE ADVISED THE NOTE REGARDING
 ARTICLE 250.83 AND 250.81 IN THE
 GROUNDING ELECTRODE CUT ON SHEET E2.2 IS
 A REFERENCE OUT OF THE 1996 NEC. THIS
 JURISDICTION HAS ADOPTED THE 2002 NEC,
 THAT IS THE CODE THAT WILL BE USED FOR
 ELECTRICAL REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/805 6731