| 2006-03-29 00:00:00 | |
| | THIS REVIEW IS FOR CONDUIT INSTALLATION |
| | ONLY, AND IS NOT A REVIEW FOR THE |
| | ELECTRIC EQUIPMENT THAT IS SHOWN |
| | DIAGRAMMATICALLY, MAINS, PANELS OR POWER |
| | POINTS. |
| | |
| | |
| | MSB-1 SHOWS A PRELIMINARY LOCATION IN |
| | THE NORTH ELECTRIC ROOM AT COLUMN LINE |
| | #5. PLEASE BE ADVISED THAT THIS ROOM |
| | WOULD NOT BEET EGRESS REQUIREMENTS OF |
| | 110.26(C)(2) FOR A 1200 AMP EQUIPMENT: |
| | |
| | LARGE EQUIPMENT. FOR EQUIPMENT RATED |
| | 1200 AMPERES OR MORE AND OVER 1.8 M (6 |
| | FT) WIDE THAT CONTAINS OVERCURRENT |
| | DEVICES, SWITCHING DEVICES, OR CONTROL |
| | DEVICES, THERE SHALL BE ONE ENTRANCE TO |
| | THE REQUIRED WORKING SPACE NOT LESS THAN |
| | 610 MM (24 IN.) WIDE AND 2.0 M (61/2 FT) |
| | HIGH AT EACH END OF THE WORKING SPACE. |
| | WHERE THE ENTRANCE HAS A PERSONNEL |
| | DOOR(S), THE DOOR(S) SHALL OPEN IN THE |
| | DIRECTION OF EGRESS AND BE EQUIPPED WITH |
| | PANIC BARS, PRESSURE PLATES, OR OTHER |
| | DEVICES THAT ARE NORMALLY LATCHED BUT |
| | OPEN UNDER SIMPLE PRESSURE. |
| | |
| | ALSO BE ADVISED THE NOTE REGARDING |
| | ARTICLE 250.83 AND 250.81 IN THE |
| | GROUNDING ELECTRODE CUT ON SHEET E2.2 IS |
| | A REFERENCE OUT OF THE 1996 NEC. THIS |
| | JURISDICTION HAS ADOPTED THE 2002 NEC, |
| | THAT IS THE CODE THAT WILL BE USED FOR |
| | ELECTRICAL REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |