Plan Review Notes
Plan Review Notes For Permit 05110709
Permit Number 05110709
Review Stop M
Sequence Number 2
Notes
Date Text
2005-12-30 00:00:00*** DENIED ***
 1) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 . PLEASE HAVE THE COMBUSTION
 AIR CAL'S. AND MECHANICAL PLANS SIGNED.
  
 2) PLEASE SHOW JOB LOCATION ON
 MECHANICAL PLANS.
  
 3) NO DUCT OPENINGS ARE PERMITTED IN A
 GARAGE, PER 2004 FBC/R 309.1.1 . THE
 GOLF CART ROOM AND THE EXERCISE ROOM
 HAVE GARAGE DOORS AND MAY BE USED AS A
 GARAGE.
  
 4) PLANS ARE CALLING FOR A VENTLESS
 FIREPLACE IN THE OUTDOOR ENTERAINMENT
 AREA MANUFACTURE'S SPEC'S. ARE FOR A
 VENTED FIREPLACE, PLEASE CORRECT.
  
 5) PLEASE SHOW AHU #4 AND COUDENSER UNIT
 #4 ON ELECTRICAL PLAN.
  
 6) MANUL J CAL'S. ARE CALLING FOR THREE
 A/C UNITS TOTALING 79,081 SENSIBLE
 BTU'S. THE MECHANICAL PLANS ARE CALLING
 FOR, FOUR A/C SYSTEMS TOTALING 106,000
 SENSIBLE BTU'S. PLEASE COMPLY WITH 2004
 FBC 13-607.1.ABC.1.1 .
  
 7) PLEACE SHOW IF AHU #4 IS GOING IN A
 CLOSET OR THE ATTIC.
  
 8) PLEASE NOTE DUCTS PENETRATING THE
 GARAGE CEILING CAN NOT BE FLEX. DUCT,
 PER 2004 FBC/R309.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.