| 2005-12-30 00:00:00 | *** DENIED *** |
| | 1) ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . PLEASE HAVE THE COMBUSTION |
| | AIR CAL'S. AND MECHANICAL PLANS SIGNED. |
| | |
| | 2) PLEASE SHOW JOB LOCATION ON |
| | MECHANICAL PLANS. |
| | |
| | 3) NO DUCT OPENINGS ARE PERMITTED IN A |
| | GARAGE, PER 2004 FBC/R 309.1.1 . THE |
| | GOLF CART ROOM AND THE EXERCISE ROOM |
| | HAVE GARAGE DOORS AND MAY BE USED AS A |
| | GARAGE. |
| | |
| | 4) PLANS ARE CALLING FOR A VENTLESS |
| | FIREPLACE IN THE OUTDOOR ENTERAINMENT |
| | AREA MANUFACTURE'S SPEC'S. ARE FOR A |
| | VENTED FIREPLACE, PLEASE CORRECT. |
| | |
| | 5) PLEASE SHOW AHU #4 AND COUDENSER UNIT |
| | #4 ON ELECTRICAL PLAN. |
| | |
| | 6) MANUL J CAL'S. ARE CALLING FOR THREE |
| | A/C UNITS TOTALING 79,081 SENSIBLE |
| | BTU'S. THE MECHANICAL PLANS ARE CALLING |
| | FOR, FOUR A/C SYSTEMS TOTALING 106,000 |
| | SENSIBLE BTU'S. PLEASE COMPLY WITH 2004 |
| | FBC 13-607.1.ABC.1.1 . |
| | |
| | 7) PLEACE SHOW IF AHU #4 IS GOING IN A |
| | CLOSET OR THE ATTIC. |
| | |
| | 8) PLEASE NOTE DUCTS PENETRATING THE |
| | GARAGE CEILING CAN NOT BE FLEX. DUCT, |
| | PER 2004 FBC/R309.1.1 . |
| | |