| 2005-12-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- ALL PLANS SUBMITTED AFTER OCTOBER 1ST |
| | 2005 ARE REQUIRED TO COMPLY WITH FBC |
| | 2004. REVISE ALL PLANS, GENERAL NOTES, |
| | DESIGN PARAMETERS, CONSTRUCTION TYPE AND |
| | ALL PERTINENT ITEMS SHOWN ON PLANS AS |
| | REQUIRED TO COMPLY WITH FBC 2004. |
| | |
| | 2- ENERGY CALCULATIONS: |
| | A) REVISE UNDER ATTIC AREA TO COMPLY |
| | WITH SEC. 13-604.1.A.1 FBC 2004. |
| | |
| | B) ENERGY CALCS ARE TO BE CALCULATED |
| | FOR WORST CASE SCENARIO OR BE SPECIFIC |
| | TO THE LOCATION OF THE HOUSE. ENERGY |
| | CALCS SUBMITTED ARE NOT FOR WORST CASE |
| | SCENARIO AND DON'T MATCH SPECIFIC |
| | ORIENTATION OF THIS HOUSE. REVISE AS |
| | REQUIRED. |
| | |
| | 3- TRUSS DESIGN DRAWINGS NEED TO BE |
| | PROVIDED TO THE BUILDING OFFICIAL FOR |
| | APPROVAL PRIOR TO INSTALLATION. SEC. |
| | R802.10.1 RESIDENTIAL FBC 2004. |
| | (REMAINDER: DESIGNER OF RECORD TO REVIEW |
| | ALL TRUSSES PRIOR TO SUBMITTAL TO THIS |
| | OFFICE). |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW ALL |
| | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO |
| | THIS OFFICE AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC 2004 |
| | |
| | 5- PROVIDE ALL INFORMATION ON PLANS |
| | REGARDING THE GARAGE SEPARATION AND |
| | OPENING PROTECTION AS REQUIRED BY SEC. |
| | R309 OF RESIDENTIAL FBC 2004. |
| | |
| | 6- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 7- AREA CALCULATIONS ON SHEET A2 DON'T |
| | INCLUDE THE EXERCISE ROOM NEXT TO THE |
| | GOLF CART AREA. ALSO, A/C PLANS SHOW |
| | GOLF CART AND EXERCISE AREAS TO BE A/C. |
| | REVISE ALL CALCULATIONS AS REQUIRED. |
| | |
| | 8- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) TRUSS CONNECTORS. PROVIDE ONLY THE |
| | COVER PAGE AND THE PAGES SHOWING THE |
| | SPECIFIC CONNECTORS THAT ARE SPECIFIED |
| | ON PLANS. PLEASE, DON'T SUBMITT ALL |
| | PRODUCT APPROVAL REPORT TO EXPEDITE THE |
| | REVIEW PROCESS AND SAVE PAPER. |
| | |
| | B) CASEMENT WINDOWS: NEED 2004 CODE |
| | VERSION FLORIDA PRODUCT APPROVAL PAGE |
| | AND THE DADE COUNTY NOA THAT MATCHES NOA |
| | SUBMITTED FOR FLORIDA APPROVAL. |
| | |
| | C) ENTRY DOORS PRODUCT APPROVAL |
| | SUBMITTED SPECIFIES ON SHEET 1 OF 5 THAT |
| | SHUTTERS ARE REQUIRED. THIS HOUSE IS |
| | SUPPOSED TO HAVE IMPACT GLAZING IN ALL |
| | DOORS AND WINDOWS. SUBMIT PROPER PRODUCT |
| | APPROVAL. |
| | |
| | D) 2" WINDOW MULLIONS: PROVIDE CURRENT |
| | 2004 CODE VERSION FLORIDA PRODUCT |
| | APPROVAL AND DADE COUNTY NOA THAT |
| | MATCHES NOA SUBMITTED FOR FLORIDA |
| | APPROVAL. |
| | |
| | E) GARAGE DOORS: NEED 2004 FLORIDA CODE |
| | VERSION. FL #542 IS NO LONGER LISTED IN |
| | THE FLORIDA WEBSITE. |
| | |
| | 9- SOIL TEST REPORT WAS DONE BASED ON |
| | FBC 2001. NEED CURRENT SOIL TEST REPORT |
| | COMPLYING WITH FBC 2004. |
| | |
| | 10- SHEET A6: PROVIDE DETAILS AND SPECS |
| | FOR GATED COURTYARD ENTRANCE |
| | CONSTRUCTION. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 11- A) REVISE REAR AND RIGHT ELEVATIONS |
| | TO SHOW BBQ AREA AND BBQ HOOD. |
| | |
| | B) FLOOR PLAN ON SHEET A2 TO |
| | INDICATE HOOD ABOVE BBQ GRILL. |
| | |
| | 12- PROVIDE BATHROOM WITH DOOR THAT |
| | ALLOWS 29" CLEAR OPENING. SEC. R322 |
| | RESIDENTIAL FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |