2005-12-29 00:00:00BUILDING REVIEW CHECKLIST:
 1- ALL PLANS SUBMITTED AFTER OCTOBER 1ST
 2005 ARE REQUIRED TO COMPLY WITH FBC
 2004. REVISE ALL PLANS, GENERAL NOTES,
 DESIGN PARAMETERS, CONSTRUCTION TYPE AND
 ALL PERTINENT ITEMS SHOWN ON PLANS AS
 REQUIRED TO COMPLY WITH FBC 2004.
  
 2- ENERGY CALCULATIONS:
 A) REVISE UNDER ATTIC AREA TO COMPLY
 WITH SEC. 13-604.1.A.1 FBC 2004.
  
 B) ENERGY CALCS ARE TO BE CALCULATED
 FOR WORST CASE SCENARIO OR BE SPECIFIC
 TO THE LOCATION OF THE HOUSE. ENERGY
 CALCS SUBMITTED ARE NOT FOR WORST CASE
 SCENARIO AND DON'T MATCH SPECIFIC
 ORIENTATION OF THIS HOUSE. REVISE AS
 REQUIRED.
  
 3- TRUSS DESIGN DRAWINGS NEED TO BE
 PROVIDED TO THE BUILDING OFFICIAL FOR
 APPROVAL PRIOR TO INSTALLATION. SEC.
 R802.10.1 RESIDENTIAL FBC 2004.
 (REMAINDER: DESIGNER OF RECORD TO REVIEW
 ALL TRUSSES PRIOR TO SUBMITTAL TO THIS
 OFFICE).
  
 4- DESIGNER OF RECORD TO REVIEW ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004
  
 5- PROVIDE ALL INFORMATION ON PLANS
 REGARDING THE GARAGE SEPARATION AND
 OPENING PROTECTION AS REQUIRED BY SEC.
 R309 OF RESIDENTIAL FBC 2004.
  
 6- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 7- AREA CALCULATIONS ON SHEET A2 DON'T
 INCLUDE THE EXERCISE ROOM NEXT TO THE
 GOLF CART AREA. ALSO, A/C PLANS SHOW
 GOLF CART AND EXERCISE AREAS TO BE A/C.
 REVISE ALL CALCULATIONS AS REQUIRED.
  
 8- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) TRUSS CONNECTORS. PROVIDE ONLY THE
 COVER PAGE AND THE PAGES SHOWING THE
 SPECIFIC CONNECTORS THAT ARE SPECIFIED
 ON PLANS. PLEASE, DON'T SUBMITT ALL
 PRODUCT APPROVAL REPORT TO EXPEDITE THE
 REVIEW PROCESS AND SAVE PAPER.
  
 B) CASEMENT WINDOWS: NEED 2004 CODE
 VERSION FLORIDA PRODUCT APPROVAL PAGE
 AND THE DADE COUNTY NOA THAT MATCHES NOA
 SUBMITTED FOR FLORIDA APPROVAL.
  
 C) ENTRY DOORS PRODUCT APPROVAL
 SUBMITTED SPECIFIES ON SHEET 1 OF 5 THAT
 SHUTTERS ARE REQUIRED. THIS HOUSE IS
 SUPPOSED TO HAVE IMPACT GLAZING IN ALL
 DOORS AND WINDOWS. SUBMIT PROPER PRODUCT
 APPROVAL.
  
 D) 2" WINDOW MULLIONS: PROVIDE CURRENT
 2004 CODE VERSION FLORIDA PRODUCT
 APPROVAL AND DADE COUNTY NOA THAT
 MATCHES NOA SUBMITTED FOR FLORIDA
 APPROVAL.
  
 E) GARAGE DOORS: NEED 2004 FLORIDA CODE
 VERSION. FL #542 IS NO LONGER LISTED IN
 THE FLORIDA WEBSITE.
  
 9- SOIL TEST REPORT WAS DONE BASED ON
 FBC 2001. NEED CURRENT SOIL TEST REPORT
 COMPLYING WITH FBC 2004.
  
 10- SHEET A6: PROVIDE DETAILS AND SPECS
 FOR GATED COURTYARD ENTRANCE
 CONSTRUCTION. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- A) REVISE REAR AND RIGHT ELEVATIONS
 TO SHOW BBQ AREA AND BBQ HOOD.
  
 B) FLOOR PLAN ON SHEET A2 TO
 INDICATE HOOD ABOVE BBQ GRILL.
  
 12- PROVIDE BATHROOM WITH DOOR THAT
 ALLOWS 29" CLEAR OPENING. SEC. R322
 RESIDENTIAL FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712